PSEN ma1.3a/b-21 VA
Operating Manual PSEN ma1.3a/b-21 VA
1004515-EN-02
9
Assured operating distance S
ao
in mm
Lateral offset
Vertical offset
0
2
4
0
8.0
7.2
5.8
2
7.2
6.6
5.1
4
5.8
5.1
3.2
The stated values are valid at a temperature of 20 °C.
Wiring
}
}
Calculation of the max. cable length l
max
:
R
lmax
- R
i
R
l
/ km
I
max
=
R
lmax
= Max. overall cable resistance (see evaluation device's technical details)
Ri = Internal resistance sensor (see
R
l
/ km = Cable resistance/km of the cable (see technical details cable)
}
Ensure the wiring and EMC requirements of EN 60204-1 are met.
}
Depending on which evaluation device is used, the overall cable resistance must be
checked; before commissioning it may also be necessary to check the cross circuit de-
tection function.
Perform the checks as described in the operating manual for the evaluation device.
}
The safety contacts are not short circuit-proof.
}
UL requirement: the supply voltage must be provided via a Class 2 power supply.
Pin assignment
The safety switch is shown in an unoperated condition.
Layout of the 6-core cable
1
2
3
4
5+
6
green
white
brown
blue
red
black
NOTICE
The auxiliary contact with LED
– may only be operated with a supply voltage of up to 24 VDC
–
cannot
be connected in series
– may
not
be used for safety circuits