PickData SEM Three Скачать руководство пользователя страница 1

 

V03-020620 

SEM Three 

 

Please note that this document is only a short user manual and does not handle every function. The complete manual is available 
at 

www.pickdata.net

 

 

  
 

TECHNICAL CHARACTERISTICS 

 

Power circuit 
Input voltage 

110 …. 264 Vac 

Frequency 

47 …. 63 Hz 

Maximum consumption 

2,5 …. 4,5 VA 

Environmental conditions 
Temperature range 

-10 …. +60ºC 

Humidity range 

5 …. 95% 

Mechanical characteristics 
Enclosure material 

Plastic UL94 – V0 Self-extinguishable  

Protection grade 

IP30 

Unit dimensions (Width x Height x Length) 

18 x 70 x 109 mm 

Weight 

70 g 

Mounting 

DIN Rail (1 module) 

Maximum working altitude 

2000 m 

Serial interface 
Type 

RS-485 three wires 

Baud rate 

9600 / 19200 / 38400 / 57600 / 115200 bps configurable  

Data bits 

8 

Parity 

Without parity / Even configurable 

Stop bits 

1 / 2 configurable 

Characteristics and electrical security 
Security 

CAT III 300 V under EN 61010 

Protection class 

Class II 

External current transformers

 

Series TRC and TRA (In / 0,250 A)

 

Standards 
Standards 

UNE EN 61010-1:2010, UNE-EN 61000-6-2, UNE-EN 61000-6-4

 

 

COMMUNICATION 

 

The device comes equipped with a RS-485 communication port to read  and write the parameters of the device or other devices 
connected. The protocol used is Modbus RTU. 
 
By default the device is configured with 

peripheral number 72 

(decimal) and 

communication mode 4 

(9600 bps, 8, N, 1). Using 

the command for changing the device number it is possible to assign any other number (maximum FF in hexadecimal or 255 in 
decimal). 
In case you 

don’t remember the slave number, you can return to default number and communication mode following this steps: 

 

Power off the device. 

 

Press permanently reset button. 

 

Power on the device and stop pressing the reset button. 

 
 

WORKING MODE 

 

SEM Three 

has 4 different working modes for measuring the electrical parameters of an installation. To 

change the working mode you must change the value of register “Working mode” between mode 0 
(default), 1, 2 or 3. Belong are shown the details of each mode: 
 

 

Mode 0: L1, L2 and L3 single-phase. Sum of all values measured in three-phase parameters. 

 

Mode 1: L2 and L3 single-phase. L1 equilibrated three-phase. Sum of all values measured in 
three-phase parameters. 

 

Mode 2: L3 single-phase. L1 and L2 equilibrated three-phase. Sum of all values measured in 
three-phase parameters. 

 

Mode 3: L1, L2 and L3 equilibrated three-phase. Sum of all values measured in three-phase 
parameters. 

 

 

 
 

Mode 0 

L1 

T

o

ta

th

re

e

-p

h

a

se

 

L2 
L3 

Mode 1 

L1 (x3) 

L2 
L3 

Mode 2 

L1 (x3) 
L2 (x3) 

L3 

Mode 3 

L1 (x3) 
L2 (x3) 
L3 (x3) 