Manual EXAM01
MA 1277-A011 EN
36
8 Service
First try to identify the technical problem. Feel free to ask our support team for help. We
are pleased to assist you.
Removal of a module:
- Switch off the
phyMOTION
™’s supply voltage
- Disconnect the supply voltage
- POWM01 or POWM02 and the MCM01 main controller module.
- Cut the red seal tape and the black label tape carefully on the left and right edge of
the module/front panel which you want to remove. Don’t slide the blade between
the front panels by no means. When backfitting by our service the red seal tape is
renewed.
- Please note the following before the removal, because up to four EXAM modules
are connected with the I4XM indexer module by a ribbon cable on the rear of the
module:
- First, loosen the front screws of all five modules (I4XM and EXAM).
-
Then pull the I4XM module carefully out of the housing by the handle
– proceed
with the four EXAM modules as well.
- Exchange the EXAM01 module.
- Then, starting with the I4XM module slide the five modules carefully back into the
guide rail. If you have problems to push the module for the last half centimeter,
move the module to the front panel slightly to the left and to the right during
sliding, so that the connector pins contact the backplane socket.
- If you want to use the
phyMOTION
™ after removing a module, the gap has to be
sealed with a blanking plate before power supply is reconnected and switched on.
- To send a module to phytron use ESD packaging only.