background image

www.UsePhoenix.com • [email protected]

Toll-Free 1-800-533-7533

3.3 Ducting

The lip on the exhaust opening of the Phoenix AirMax is 

designed to accommodate layflat ducting with 14” or larger 

diameter.

3.4 Resettable Circuit Breaker

The 12 Amp thermal circuit breaker protects the unit and 

devices connected to its duplex GFCI receptacle.  In case of a 

fault, the breaker can be reset at the Phoenix AirMax control 

panel.
Use of multiple fans and any other connected devices must 

be in accordance with the National Electric Code and any 

additional codes or laws required by your local government.

IMPORTANT: Total amperage of the Phoenix AirMax plus all 
devices plugged into its convenience receptacle is limited 
by the onboard circuit breaker.  Excessive current will cause 
the circuit breaker to trip.  This may occur instantly or after 
a period of time depending on the operating conditions.

IMPORTANT: When the Phoenix AirMax is plugged into a 
standard “powered” wall outlet the Phoenix AirMax’s duplex 
outlet is electrically “HOT” and AC voltage is present.

3.5 GFCI Protection and the On-Board Duplex 
Receptacle

The on-board convenience receptacle provides electrical 

shock protection for the operator in damp or wet applications 

or other conditions that would cause a ground fault.  The 

Phoenix AirMax is wired to branch protect all on-board 

components in addition to protecting any fans or other 

equipment plugged into the onboard receptacle. 
Testing GFCI operation can be done by pressing the “TEST” 

button located on the GFCI duplex outlet.  If operating 

properly, the “RESET” button will pop out.  In addition, 

notice that the fan will NOT operate if the GFCI outlet is in 

the TRIPPED condition as the motor and other on-board 

components are included in the GFCI protected circuit.
The GFCI circuit can only be “RESET” when the Phoenix 

AirMax is connected to a properly grounded wall outlet 

providing the rated voltage.

4 Maintenance

WARNING: Disconnect the unit from power before servicing 

or cleaning.  Replace all safety grills after servicing or 

cleaning

4.1 Power Cord

Visually inspect cord and plug head before use.  If there are 

signs of damage or excessive wear, discontinue use until the 

unit has been serviced.

4.2 Cleaning

The housing is made of durable and washable polypropylene. 

When cleaning, the use of solvents is NOT recommended.
When washing inside the unit, disconnect the unit from its 

power source.  Protect the switch, receptacle and circuit 

breaker from water intrusion.  Do not spray water or cleaning 

solution at motor.  If motor does get wet, allow motor to dry 

completely before restarting.  If fan is to be washed and not 

used within 24 hours, allow fan to drip dry for 10 minutes 

and then run for 5 minutes before storing.

IMPORTANT:  Do NOT remove impeller blade from 
motor assembly.  Doing so can cause blade to become 
imbalanced upon re-assembly.

4.3 Service

CAUTION: Servicing the Phoenix AirMax with its high voltage 

circuitry presents a health hazard that could result in death, 

serious bodily injury, and/or property damage.  Disconnect 

the appliance from the power supply before servicing.  Only 

qualified service people should service this unit. 

CAUTION: If the supply cord or GFCI become damaged, they 

must be replaced by the manufacturer, its service agent or 
similarly qualified person in order to avoid a hazard.

Содержание AirMax

Страница 1: ...This gives you high velocity air over a 25 larger area than other low profile air movers In addition the Phoenix AirMax is stable on all 5 sides for maximum flexibility to position and direct the drying The Phoenix AirMax is the safest fan in its class providing a quality GFCI convenience receptacle that protects not only connected loads but onboard components as well This is unlike competing fans...

Страница 2: ...tant Safety Instructions CAUTION Risk of electric shock Can cause injury or death to reduce the risk of electric shock Do not expose to standing water or rain Do not use an extension cord Unplug fan before servicing Do not block air intake or outlet One foot minimum distance to obstructions Indoor use only Do not use as stool or bench Do not operate with damaged cord or plug Do not run cord under ...

Страница 3: ...rly the RESET button will pop out In addition notice that the fan will NOT operate if the GFCI outlet is in the TRIPPED condition as the motor and other on board components are included in the GFCI protected circuit The GFCI circuit can only be RESET when the Phoenix AirMax is connected to a properly grounded wall outlet providing the rated voltage 4 Maintenance WARNING Disconnect the unit from po...

Страница 4: ...ix com sales UsePhoenix com Toll Free 1 800 533 7533 5 Wiring Diagram HOT NEUTRAL LOAD LINE GFCI DUPLEX YEL GROUNDED PLUG WHT BLK WHT BLK POWER SWITCH BRN PUR FAN MOTOR 12 AMP CIRCUIT BREAKER 20 µF CAPACITOR PUR PUR ...

Страница 5: ...ion 4035662 Impeller Assembly 4036557 Power Cord Kit 20 cord bolts nuts 4035235 08 Run Capacitor 20 mfd 370 VAC 4035665 Rubber Feet 4036256 Duplex GFCI Outlet Kit 4035825 Rocker Switch 4035752 12A Circuit Breaker 4037469 Inlet Grill 4036486 20 Cord Only Optional Parts 4024936 Duct Lay Flat 14 x 250 ...

Страница 6: ...6 www UsePhoenix com sales UsePhoenix com Toll Free 1 800 533 7533 This page intentionally left blank ...

Страница 7: ...ir or installation accident acts of nature or any other cause beyond Therma Stor Products reasonable control Limitations and Exclusions If any AirMax Fan part is repaired or replaced the new part shall be warranted for only the remainder of the original warranty period applicable thereto but all warranty periods will be extended by the period of time if any that the AirMax Fan is out of service wh...

Отзывы: