background image

Interfaces of the Device

8095_en_00

PHOENIX CONTACT

4-7

4.2.2

RS232 (X6)

The interface can be used for any type of application.

4.2.2.1

Pin Assignment

Figure 4-6

25 pin D-SUB female connector strip

Connector in the operating terminal: 25-pin D-SUB female connector

4.2.2.2

Termination

NOTICE

The use of this interface is not certified for maritime applications!

Table 4-6

Pin assignment RS232

Pin

Designation

Function

6

TD

Transmitted Data

15

CTS

Clear to Send

17

RTS

Request to Send

18

RD

Received Data

25

SGND

Signal Ground

NOTICE

The D-SUB connector strips must be shielded sufficiently. See chapter „Shielding D-SUB 

Connectors“ on page 4-19.

NOTICE

When the interface is operated as a RS232, the termination for the RS485 must be 

switched OFF.

Содержание UM EN TP 3 Series

Страница 1: ...AUTOMATION User Manual UM EN TP 3xxx Touch Panel with TFT Display...

Страница 2: ......

Страница 3: ...ser Manual 06 2010 Designation Revision Order No UM EN TP 3xxx 00 This user manual is valid for Designation Art No TP 3057M TP 3057T TP 3070T TP 3105T TP 3121T 2700901 2700905 2700906 2700910 2700911...

Страница 4: ...or printing errors in the information cannot be ruled out Phoenix Contact does not offer any guarantees as to the reliability accuracy or completeness of the information All information made availabl...

Страница 5: ...s Internet Up to date information on Phoenix Contact products and our Terms and Conditions can be found on the Internet at www phoenixcontact com Make sure you always use the latest documentation It c...

Страница 6: ...TP 3057M TP 3057T TP 3070T TP 3105T TP 3121T PHOENIX CONTACT 8095_en_00...

Страница 7: ...24 V 2 14 2 4 Switching On 2 17 2 4 1 Loading Procedure on Windows CE Operating System 2 17 Control and Display Elements 3 1 3 1 Touchscreen 3 1 3 2 Key Reset 3 1 3 3 Display 3 1 Interfaces of the Dev...

Страница 8: ...nance and Servicing 5 1 5 1 Maintenance Interval 5 1 5 2 Front Panel 5 1 5 3 Fuse 5 1 5 4 Battery 5 1 5 4 1 Changing the Battery 5 2 5 4 2 Battery Disposal 5 3 Technical Data 6 1 6 1 Generally 6 1 6 2...

Страница 9: ...on and operation must only be carried out by qualified and trained personnel This is the safety alert symbol It is used to alert you to potential personal injury hazards Obey all safety messages that...

Страница 10: ...commissioning operating and maintenance work in connection with the automation system must be performed by trained personnel only e g qualified electricians electrical engineers etc The configuration...

Страница 11: ...e front Figure 2 1 Mounting the device using a mounting bracket 2 Insert the mounting brackets into the appropriate openings figure 1 and pull the brack ets downwards until they lock in place figure 2...

Страница 12: ...TP 3057M TP 3057T TP 3070T TP 3105T TP 3121T 2 2 PHOENIX CONTACT 8095_en_00 3 Fasten the device into position using the threaded pins figure 3...

Страница 13: ...Installation and Commissioning 8095_en_00 PHOENIX CONTACT 2 3 2 2 1 Front Panel Dimensions Figure 2 2 TP 3057M TP 3057T...

Страница 14: ...TP 3057M TP 3057T TP 3070T TP 3105T TP 3121T 2 4 PHOENIX CONTACT 8095_en_00 Figure 2 3 TP 3070T...

Страница 15: ...Installation and Commissioning 8095_en_00 PHOENIX CONTACT 2 5 Figure 2 4 TP 3105T...

Страница 16: ...TP 3057M TP 3057T TP 3070T TP 3105T TP 3121T 2 6 PHOENIX CONTACT 8095_en_00 Figure 2 5 TP 3121T...

Страница 17: ...Installation and Commissioning 8095_en_00 PHOENIX CONTACT 2 7 2 2 2 Mounting Cutout Figure 2 6 TP 3057M TP 3057T TP 3070T A Mounting Cutout B Front Panel...

Страница 18: ...TP 3057M TP 3057T TP 3070T TP 3105T TP 3121T 2 8 PHOENIX CONTACT 8095_en_00 Figure 2 7 TP 3105T A Mounting Cutout B Front Panel...

Страница 19: ...Installation and Commissioning 8095_en_00 PHOENIX CONTACT 2 9 Figure 2 8 TP 3121T A Mounting Cutout B Front Panel...

Страница 20: ...T TP 3105T TP 3121T 2 10 PHOENIX CONTACT 8095_en_00 2 2 3 Side View Mounting Depth Figure 2 9 TP 3057M TP 3057T 1 Mounting Bracket 2 Threaded Pin 3 Mounting Surface Thickness 1 mm to 6 mm 4 Circumfere...

Страница 21: ...Installation and Commissioning 8095_en_00 PHOENIX CONTACT 2 11 Figure 2 10 TP 3070T 1 Mounting Bracket 2 Threaded Pin 3 Mounting Surface Thickness 1 mm to 6 mm 4 Circumferential Seal 5 Front Panel...

Страница 22: ...57M TP 3057T TP 3070T TP 3105T TP 3121T 2 12 PHOENIX CONTACT 8095_en_00 Figure 2 11 TP 3105T 1 Mounting Bracket 2 Threaded Pin 3 Mounting Surface Thickness 1 mm to 6 mm 4 Circumferential Seal 5 Front...

Страница 23: ...Installation and Commissioning 8095_en_00 PHOENIX CONTACT 2 13 Figure 2 12 TP 3121T 1 Mounting Bracket 2 Threaded Pin 3 Mounting Surface Thickness 1 mm to 6 mm 4 Circumferential Seal 5 Front Panel...

Страница 24: ...upply voltage Connector in the operating device 3 pin connector A suitable female connector strip is supplied Table 2 1 Pin assignment supply voltage Pin Designation Function 1 Low Noise Ground 2 0 V...

Страница 25: ...o connect the device to the supply voltage 1 Strip approx 30 mm 1 181 off the outer cable sheath and approx 5 mm 0 197 off the wires Figure 2 13 Preparing the cable 2 Fit the wires with wire end ferru...

Страница 26: ...e connector strip is plugged on 4 Secure the female connector strip in place with a screw type locking to prevent it from slipping out NOTICE Damage A separate conductor must always be provided for th...

Страница 27: ...buttons The touch panel has two operating modes Normal no button pressed Setup Main Press For Setup Main Menu button pressed 2 4 1 1 Normal Mode The program AppStarter exe starts from the internal Fl...

Страница 28: ...minutes OK Cancel Change Display Mode A OK Cancel A A A LCD Saver Current Mode Copy to Flash Copy to USB Import Settings Home Copy USB Stick Change Display Mode Start Calibration SNTP Settings Display...

Страница 29: ...n this directory In this case the flash registry is always deactivated so that the image is processed with a new default registry Update Update Bootloader If the bootloader subdirectory on the USB sti...

Страница 30: ...roperties Select a background image or browse a user specific graphic for the background You can define the appearance of the surface with the tab You can depending on the power supply external batter...

Страница 31: ...000 000 000 000 DNS Secondary DNS OK Cancel WINS OK Cancel Primary WINS 000 000 000 000 000 000 000 000 Secondary WINS DHCP enabled Save registry and restart device to work with new parameters DHCP Up...

Страница 32: ...o be password protected Network Settings Current IP Displays the current IP address subnet mask device name DHCP status and the gateway Network Settings DHCP You may enable DHCP service You must save...

Страница 33: ...ation Date Time OK Apply Current Time 15 00 00 AM X Time Zone GMT 01 00 Amsterdam Berlin Bern Rome Automatically adjust clock for daylight saving Current Password Password OK Change Cancel Enable Pass...

Страница 34: ...nd time Press Refresh to update the values Settings Password The password can be activated deactivated or redefined When the password is activated all password protected dialog boxes can only be acces...

Страница 35: ...erating device is equipped with different displays depending on variant NOTICE Damage Pointed or sharp objects such as pens or fingernails can lead to irreparable damages of the touch screen Exclusive...

Страница 36: ...TP 3057M TP 3057T TP 3070T TP 3105T TP 3121T 3 2 PHOENIX CONTACT 8095_en_00...

Страница 37: ...andard Interfaces Figure 4 1 Standard interfaces 1 Compact Flash Inserted on the Side on the Operating Device 2 Female Connector X5 Ethernet on the Side of the Operating Device 3 Female Connector X9 X...

Страница 38: ...nterface Pin Designation Function 1 Tx Transmitted Data Positive Polarity 2 Tx Transmitted Data Negative Polarity 3 Rx Received Data Positive Polarity 4 n c Not Connected 5 n c Not Connected 6 Rx Rece...

Страница 39: ...s For maritime applications the use of the USB interfaces is allowed for servicing operations only NOTICE Using input devices not suitable for industrial use e g keyboard mouse may decrease safety of...

Страница 40: ...fic use only allows one of the three interface standards to be used Figure 4 3 RS422 RS485 RS232 1 Compact Flash Inserted on the Side on the Operating Device 2 Female Connector X5 Ethernet on the Side...

Страница 41: ...connector strip Connector in the operating terminal 25 pin D SUB female connector NOTICE The use of this interface is not certified for maritime applications Signal Logic 1 UA UB 0 3 V i e UA UB Signa...

Страница 42: ...d Figure 4 5 Block diagram termination RS485 Legend for table I Switch ON Switch OFF Table 4 4 Resistance values termination RS485 Designation Value R1 R3 510 Ohm R2 150 Ohm R4 120 Ohm NOTICE The swit...

Страница 43: ...Termination NOTICE The use of this interface is not certified for maritime applications Table 4 6 Pin assignment RS232 Pin Designation Function 6 TD Transmitted Data 15 CTS Clear to Send 17 RTS Reque...

Страница 44: ...ide on the Operating Device 2 Female Connector X5 Ethernet on the Side of the Operating Device 3 Female Connector X9 X10 USB Host Type A 4 Slope Control Switch 5 Diagnostics LED 6 Female Connector X6...

Страница 45: ...le and female connector strip Table 4 7 Pin assignment CAN Pin Designation Function 1 nc Not Connected 2 CAN_L CAN_L Bus Line Dominant LOW 3 CAN_GND CAN Ground 4 nc Not Connected 5 nc Not Connected 6...

Страница 46: ...N Switch OFF X Any position NOTICE A shielded twisted pair cable cable type LiYCY TP complying with ISO 11898 must be used Table 4 8 Cable characteristics CAN Parameters Value Impedance Min 108 Ohm No...

Страница 47: ...following functions 4 3 1 5 Slope Control The Slope Control switch is located on the rear of the operating device You can use the Slope Control switch to set the edge steepness of the signals By defa...

Страница 48: ...ted on the Side on the Operating Device 2 Female Connector X5 Ethernet on the Side of the Operating Device 3 Female Connector X9 X10 USB Host Type A 4 Diagnostics LED 5 Female Connector X6 MPI 6 Conne...

Страница 49: ...Control Signal Plus 5 DGND Data Transmission Potential 6 VP Supply Voltage of Terminators Plus 7 nc Not Connected 8 RxD TxD N Received Data Transmitted Data Minus 9 CNTR N Repeater Control Signal Minu...

Страница 50: ...nnections only activate the termination at the cable end For spur lines always deactivate the termina tion 4 3 2 4 Diagnostics A diagnostics LED is located on the rear of the operating device The LED...

Страница 51: ...the Side on the Operating Device 2 Female Connector X5 Ethernet on the Side of the Operating Device 3 Female Connector X9 X10 USB Host Type A 4 Diagnostics LED 5 Female Connector X6 PROFIBUS DP 6 Con...

Страница 52: ...NTR P Repeater Control Signal Plus 5 DGND Data Transmission Potential 6 VP Supply Voltage of Terminators Plus 7 nc Not Connected 8 RxD TxD N Received Data Transmitted Data Minus 9 CNTR N Repeater Cont...

Страница 53: ...ted into the connector and can be connected 4 3 3 4 Diagnostics A diagnostics LED is located on the rear of the operating device The LED shows the states of the bus system The diagnostics LED on the o...

Страница 54: ...rojects between the PC and the operating device You can recognize the rear side of a CompactFlash card by the notches on each side of the card Figure 4 14 Rear view of the memory card 4 4 1 Inserting...

Страница 55: ...Shielding D SUB Connectors You must shield D SUB connectors as follows Figure 4 17 Shielding D SUB connectors 1 D SUB connector 2 Shield 3 Cable clip 4 Cable The shield must be folded back into a fla...

Страница 56: ...TP 3057M TP 3057T TP 3070T TP 3105T TP 3121T 4 20 PHOENIX CONTACT 8095_en_00...

Страница 57: ...to re generate At an ambient temperature of 20 C 68 F the regeneration takes approximately 20 seconds The higher the ambient temperature the longer the regeneration takes 5 4 Battery The built in bat...

Страница 58: ...sten the new battery on the inside of the enclosure 11 Disconnect the connector strip of the supply voltage 12 Place the enclosure back onto the device 13 Place the interface plate onto the enclosure...

Страница 59: ...free of charge after use at the place of purchase According to the 11 of the battery law final consumers are obligedly to give old batteries back to gathering points which attached to the common take...

Страница 60: ...TP 3057M TP 3057T TP 3070T TP 3105T TP 3121T 5 4 PHOENIX CONTACT 8095_en_00...

Страница 61: ...1 CCITT V 28 transmission length 0 15 m conductors layered in strands shielded galvanically isolated Field Bus Slave Interfaces X6 Variable baud rates and data formats CAN In accordance with ISO 11898...

Страница 62: ...EN 61000 4 4 EN 61000 4 5 EN 61000 4 6 EN 61000 6 2 Emitted interference EN 50011 limit class value A Equipment requirements EN 61131 Storage and transportation EN 61131 part 2 Power supply EN 61131...

Страница 63: ...umption typical at 24 V 0 4 A Power consumption maximum 0 6 A Connected load 9 6 W Fuse Semiconductor fuse self resetting Protection against polarity reversal Integrated Front Panel and Enclosure Encl...

Страница 64: ...ower consumption typical at 24 V 0 5 A Power consumption maximum 0 8 A Connected load 12 W Fuse Semiconductor fuse self resetting Protection against polarity reversal Integrated Front Panel and Enclos...

Страница 65: ...typical at 24 V 0 7 A Power consumption maximum 1 0 A Connected load 16 8 W Fuse Semiconductor fuse self resetting Protection against polarity reversal Integrated Front Panel and Enclosure Enclosure S...

Страница 66: ...r consumption typical at 24 V 0 7 A Power consumption maximum 1 0 A Connected load 16 8 W Fuse Semiconductor fuse self resetting Protection against polarity reversal Integrated Front Panel and Enclosu...

Страница 67: ...pical at 24 V 0 7 A Power consumption maximum 1 0 A Connected load 16 8 W Fuse Semiconductor fuse self resetting Protection against polarity reversal Integrated Front Panel and Enclosure Enclosure Ste...

Страница 68: ...TP 3057M TP 3057T TP 3070T TP 3105T TP 3121T 6 8 PHOENIX CONTACT 8095_en_00...

Страница 69: ...lave 4 15 RS232 4 7 RS422 4 5 RS485 4 5 USB 4 3 L Loading procedure on Windows CE operating system 2 17 M Maintenance 5 1 Maintenance interval 5 1 Memory card 4 18 Mounting 2 1 N Normal operating mode...

Страница 70: ...TP 3057M TP 3057T TP 3070T TP 3105T TP 3121T A 2 PHOENIX CONTACT 8095_en_00 Termination CAN 4 10 MPI 4 14 PROFIBUS 4 17 RS232 4 7 RS485 4 6 Touchscreen 3 1 U Unpacking 2 1...

Отзывы: