The I/O data of the extension module and the diagnostic data is stored in the internal
Modbus memory map of the wireless module. Each wireless module with I/O extension
modules has its own Modbus address. In addition, the diagnostic data from all wireless
devices can be read from the master wireless module.
Each wireless module must be configured using the PSI-CONF software (from page 74
onwards).
5.3
Setting the address of the wireless module via the
thumbwheel
Set the desired station address with the yellow thumbwheel on the wireless module. There
must be one master (RAD ID = 01) and at least one repeater/slave (RAD ID = 02 ... 99) in a
network.
The following settings can be made using the yellow thumbwheel:
5.4
Configuration via CONFSTICK
By default upon delivery, all wireless modules have the same network ID and the same
RF band. Using a configuration memory (CONFSTICK), you can configure a unique and
secure network without the need for software.
The CONFSTICK is used as a network key. Its network address (network ID) is unique and
cannot be assigned via the PSI-CONF software. Only wireless modules with the same
network ID are allowed to connect with each other.
Each individual network device must be configured. Only one CONFSTICK is needed for all
wireless modules in the network. After configuration, remove the CONFSTICK from the
wireless module.
Unique addressing is required in a network. If two wireless modules have the same
address in a network, the network will not function properly.
Setting the address via the thumbwheel has priority over setting the address via the
PSI-CONF software.
After making any change to the module address, press the SET button for one second to
apply the setting.
Thumbwheel
setting
Description
01
Master address
02 ... 99
Slave address
00
Not permitted
Addressing wireless modules using the PSI-CONF software (address
1 ... 250)
IDs 100 to 250 must be configured using PSI-CONF software
WARNING: Explosion hazard when used in potentially explosive areas
Do
not
insert or remove the CONFSTICK in a potentially explosive atmosphere.