Temperature inputs
Temperature inputs are available only on the optional I/O expansion module. The
connection method varies depending upon the type of sensor being connected.
Figure 2-28
PT100/PT1000 connection
Figure 2-29
Thermocouple connection
Each input channel has signal (Ax), sense (Bx) and return (Cx) terminals, where x indicates
the channel number. A common ground is available to attach the shield.
Only two- and three-wire sensors can be utilized.
A0 B0 C0
A1 B1 C1
A0
+
B0
-
+
-
C0
A1 B1 C1