![Phoenix Contact Nanoline NLC-035-024D-04I-02QRD-05A Скачать руководство пользователя страница 10](http://html1.mh-extra.com/html/phoenix-contact/nanoline-nlc-035-024d-04i-02qrd-05a/nanoline-nlc-035-024d-04i-02qrd-05a_user-manual_1551427010.webp)
Nanoline
6
PHOENIX CONTACT
2338_en_O
Figure 1-2
Nanoline base unit type codes
1.1.1
Nanoline base unit
The base unit contains the processing capability of the Nanoline system. One base unit is
required for each Nanoline control system. Power connections are made to the base unit
and distributed to the various modules from the base unit. The base unit also contains
connection points (terminals) for the input and output devices that are controlled or
monitored.
NLC-05…
A maximum of three I/O expansion modules can be attached to a base unit.
Two option slots are available on the base unit to install base unit option modules. D-SUB 9
connectors are located on each side of the unit. The left-side connector is for
communication expansion modules, and the right-side connector is for I/O expansion
modules. Both connectors are female to prevent improper module connection.
The power requirements and input/output (I/O) mix determine the model of base unit used.
NLC-03…
The NLC-03… base unit has an integrated RJ12 connector as a connection point for
programming, RS-232 or RS-485 2-wire communication. D-SUB 9 connectors are located
on each side of the base unit. The left-side connector is for communication modules and the
right-side connector allows connection of one NLC-IOX… expansion module.
1.1.2
I/O expansion modules
In addition to the I/O points located on the base unit, I/O expansion modules (NLC-IO-…)
can be connected to the base unit to provide additional connection points. Different I/O
modules provide different combinations and types of I/O.
nLC-050-024D-06I-04QRD-05A
Product Family
Type
Power Supply Type
A = AC
D = DC
X = AC/DC
Power Supply Voltage
024 = 24 volts
100 = 100-240 volts
Max Output Current*
00 = less than 1 amp
01 = 1 amp or less
05 = 5 amps or less
Output Type*
TN = Transistor, NPN
TP = Transistor, PNP
TX = Transistor, PNP and NPN
RD = Relay, DC
RA = Relay, AC
RX = Relay, AC or DC
Number of Digital Inputs*
Number of Digital Outputs*
* optional component
Содержание Nanoline NLC-035-024D-04I-02QRD-05A
Страница 1: ...User manual Installing and using Nanoline controllers UM EN NLC...
Страница 8: ...Nanoline 4 PHOENIX CONTACT 2338_en_O...
Страница 38: ...Nanoline 34 PHOENIX CONTACT 2338_en_O...
Страница 54: ...Nanoline 50 PHOENIX CONTACT 2338_en_O...
Страница 66: ...Nanoline 62 PHOENIX CONTACT 2338_en_O...
Страница 94: ...Nanoline 90 PHOENIX CONTACT 2338_en_O...
Страница 126: ...Nanoline 122 PHOENIX CONTACT 2338_en_O...