Description of the Inline controller
6959_en_07
PHOENIX CONTACT
27
2.11
Mounting and removing the Inline controller
An Inline station is set up by mounting the individual components side by side. No tools are
required. Mounting the components side by side automatically creates potential and bus
signal connections between the individual station components.
The controller is mounted perpendicular to the DIN rail.
Mounting location
Like all other terminals in the Inline product range, the Inline controller has IP20 protection
and is designed for use in a closed control cabinet or control box (terminal box) with IP54
protection or higher.
DIN rail
The Inline controller is mounted on a 35 mm standard DIN rail.
End brackets
Mount end brackets on both sides of the Inline station. The end brackets ensure that the
Inline station is correctly mounted. End brackets secure the station on both sides and keep
it from moving from side to side on the DIN rail. Phoenix Contact recommends using
CLIPFIX 35-5 end brackets (Order No. 3022276).
End plate
The mechanical end of an Inline station is the end plate. It has no electrical function. It
protects the station against ESD pulses and the user against dangerous contact voltages.
The end plate is supplied together with the Inline controller and does not need to be ordered
separately.
Mounting position
Mount the Inline controller horizontally (as shown in Figure 2-13). The temperature range
specified in the “Ambient conditions” section in “Technical data and ordering data” on
page 81 is only guaranteed if the Inline controller is mounted in this position.
For notes and instructions on mounting and removing Inline terminals, please refer to the
IB IL SYS PRO UM E user manual (for INTERBUS), the IL SYS INST UM E Inline
installation manual or the Inline system manual for your bus system.
NOTE:
Before mounting or removing the controller, make sure that the supply voltage is switched
off and cannot be switched on again by unauthorized persons.
Fix the DIN rail on which the Inline controller is mounted in several places, especially in
the area around the Inline controller. This makes it easier to remove the Inline controller.
NOTE: Damage to the Inline terminal from neighboring components
When mounting or removing the Inline controller it must be tilted. If when mounting or
removing an Inline controller an Inline terminal is located immediately to the right of the
controller, the snap-in hooks and jumper contacts may get damaged.
•
Remove the Inline terminal to the right of the Inline controller before mounting or
removing the Inline controller.
Содержание ILC 330 Series
Страница 1: ...User manual Installing and operating the ILC 330 and ILC 350 Inline controllers...
Страница 8: ...ILC 330 350 8 PHOENIX CONTACT 6959_en_07...
Страница 10: ...ILC 330 350 10 PHOENIX CONTACT 6959_en_07...
Страница 42: ...ILC 330 350 42 PHOENIX CONTACT 6959_en_07...
Страница 68: ...ILC 330 350 68 PHOENIX CONTACT 6959_en_07...
Страница 80: ...ILC 330 350 80 PHOENIX CONTACT 6959_en_07...
Страница 96: ...ILC 330 350 96 PHOENIX CONTACT 6959_en_07 T Terminal box 27 U Update 9 43 Updating the firmware 89...