IB IL 24 PSDO 8-PAC
PHOENIX CONTACT
7619_en_05
Safety characteristic data according to EN ISO 13849-1
Achievable performance level
PL d (single-channel)
PL e (two-channel)
Depends on the parameterization and wiring (see Section
“Connection options for actuators depending on the param-
eterization” on page 22 and Section “Connection examples
Diagnostic coverage (DC)
99 %
Mean time to dangerous failure (MTTFd)
For single-channel assignmennt: 100 years
For two-channel assignmennt: 100 years
Supply voltage U
L
(logic)
Current consumption
230 mA, maximum
The safety terminal is supplied with communications power via the bus coupler or a designated power terminal
in the station. Potential routing is used for the communications power in the Inline station. For the technical
data, please refer to the data sheet for the bus coupler or power terminal used.
Supply voltage: U
M
(actuators)
Nominal voltage
24 V DC according to EN 61131-2 and EN 60204
Tolerance
-15%/+20% including an entire AC voltage component with
peak value of 5%
Ripple
3.6 V
PP
Permissible voltage range
19.2 V DC to 30.0 V DC, including all tolerances, ripple in-
cluded
Current consumption
30 mA, typical (all outputs set) (plus actuator current)
Permissible interrupt time
10 ms
Within this time, the output voltage for the safe outputs fails
as the outputs are not internally buffered.
The safety terminal is supplied with main voltage U
M
via the bus coupler or a power terminal in the station.
Potential routing is used for the main voltage in the Inline station. For the technical data, please refer to the
data sheet for the bus coupler or power terminal used.
WARNING: Loss of the safety function when using unsuitable power supplies
Only use power supplies according to EN 50178/VDE 0160 (PELV).
Содержание IB IL 24 PSDO 8-PAC
Страница 1: ...User manual IB IL 24 PSDO 8 PAC Inline module with safe digital outputs...
Страница 16: ...IB IL 24 PSDO 8 PAC 16 112 PHOENIX CONTACT 7619_en_05...
Страница 32: ...IB IL 24 PSDO 8 PAC 32 112 PHOENIX CONTACT 7619_en_05...
Страница 38: ...IB IL 24 PSDO 8 PAC 38 112 PHOENIX CONTACT 7619_en_05...
Страница 54: ...IB IL 24 PSDO 8 PAC 54 112 PHOENIX CONTACT 7619_en_05...
Страница 68: ...IB IL 24 PSDO 8 PAC 68 112 PHOENIX CONTACT 7619_en_05...
Страница 78: ...IB IL 24 PSDO 8 PAC 78 112 PHOENIX CONTACT 7619_en_05...
Страница 80: ...IB IL 24 PSDO 8 PAC 80 112 PHOENIX CONTACT 7619_en_05...
Страница 90: ...IB IL 24 PSDO 8 PAC 90 112 PHOENIX CONTACT 7619_en_05...
Страница 106: ...IB IL 24 PSDO 8 PAC 106 112 PHOENIX CONTACT 7619_en_05...