Parameterization of the safety module
7619_en_05
PHOENIX CONTACT
5
Parameterization of the safety module
5.1
Parameterization in an INTERBUS-Safety system
Parameterization includes the following:
–
Specifying the location ID via the or PC WorX software
–
Parameterizing outputs using the SafetyProg software
Location ID
The location ID is a unique ID for the safety module in the INTERBUS structure.
The location ID is automatically assigned to each safety module in the or PC WorX
software. If required, the assigned location ID can be modified later.
The location ID can be freely selected between 1 and 126. Each location ID within the IN-
TERBUS-Safety system can only be assigned once. It is transmitted to the module along
with the safe parameterization data when downloading the safe application program.
Parameterization of out-
puts
The parameterization of the safe outputs determines the behavior of the module and thus
has a considerable effect on the safety integrity level that can be achieved.
To parameterize the module, the parameterization of the safe INTERBUS controller created
in SafetyProg is automatically written to the module on every power up or reset. The supply
voltage must be present and INTERBUS must be in the RUN state.
The module cannot be operated if it is not parameterized.
In this case, the FS LED flashes.
The module is ready to operate if the parameters for all outputs are valid and transmitted
without errors. Valid output data is only written in this state. In any other state, every output
is set to the safe state.
If errors are detected during parameterization, the parameterization data is not transmitted.
The invalidity of the parameterization is indicated on the module by the flashing FS LED. In
addition, errors are indicated at the safe INTERBUS controller. In this case, check and cor-
rect the settings.
For additional information, please refer to the UM EN INTERBUS-SAFETY SYS user
manual.
Содержание IB IL 24 PSDO 8-PAC
Страница 1: ...User manual IB IL 24 PSDO 8 PAC Inline module with safe digital outputs...
Страница 16: ...IB IL 24 PSDO 8 PAC 16 112 PHOENIX CONTACT 7619_en_05...
Страница 32: ...IB IL 24 PSDO 8 PAC 32 112 PHOENIX CONTACT 7619_en_05...
Страница 38: ...IB IL 24 PSDO 8 PAC 38 112 PHOENIX CONTACT 7619_en_05...
Страница 54: ...IB IL 24 PSDO 8 PAC 54 112 PHOENIX CONTACT 7619_en_05...
Страница 68: ...IB IL 24 PSDO 8 PAC 68 112 PHOENIX CONTACT 7619_en_05...
Страница 78: ...IB IL 24 PSDO 8 PAC 78 112 PHOENIX CONTACT 7619_en_05...
Страница 80: ...IB IL 24 PSDO 8 PAC 80 112 PHOENIX CONTACT 7619_en_05...
Страница 90: ...IB IL 24 PSDO 8 PAC 90 112 PHOENIX CONTACT 7619_en_05...
Страница 106: ...IB IL 24 PSDO 8 PAC 106 112 PHOENIX CONTACT 7619_en_05...