FL NAT SMN 8TX(-M)
2-4
PHOENIX CONTACT
7966_en_04
2.2.2
Alarm contact
The FL NAT SMN 8TX(-M) has a floating alarm contact. When opening the contact, an error
is reported.
Figure 2-5
Basic circuit diagram for the alarm contact
The indicated error states are configured in web-based management or via SNMP. For a list
of error states that can be configured, please refer to Section ““Diagnostics/Alarm Contact”
2.2.3
Assignment of the RJ45 Ethernet connectors
In the event of non-redundant power supply, the device indicates a supply voltage failure
by opening the alarm contact. This error message can be prevented by connecting the
supply voltage to both terminal blocks in parallel, as shown in Figure 2-3, or by
deactivating redundant power supply monitoring in web-based management or via
SNMP.
Table 2-1
Pin assignment of RJ45 connectors
Pin number
10Base-T/10 Mbps
100Base-T/100 Mbps
1
TD+ (Transmit)
TD+ (Transmit)
2
TD- (Transmit)
TD- (Transmit)
3
RD+ (Receive)
RD+ (Receive)
4
-
-
5
-
-
6
RD- (Receive)
RD- (Receive)
7
-
-
8
-
-
R1
R2
67842015