Technical data and ordering data
108928_en_02
PHOENIX CONTACT
77 / 84
Axioline F local bus supply (U
Bus
)
Supply voltage
5 V DC (via bus base module)
Current consumption
140 mA, maximum (@ U
Bus
5 V DC)
101 mA, typical (@ U
Bus
5 V DC)
Communications power of the Smart Elements (U
SE
)
Supply voltage
3.3 V DC (using card edge connectors)
Current consumption
144 mA, maximum (@ U
SE
3.3 V DC)
92 mA, typical (@ U
SE
3.3 V DC)
I/O supply U
P
Nominal supply voltage
24 V DC (using card edge connectors)
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, ripple included)
Current consumption
12 mA, maximum (supply from U
P
with 30 V DC, all inputs set,
without supply to the sensors via clock supplies OUT_T1 and
OUT_T2)
9 mA, typical (supply from U
P
with 24 V DC, all inputs set, with
-
out supply to the sensors via clock supplies OUT_T1 and OUT
-
_T2)
8 mA, minimum (supply from U
P
with 19.2 V DC, all inputs set,
without power supply to the sensors via clock supplies OUT_T1
and OUT_T2)
Power consumption
360 mW, maximum
216 mW, typical
154, minimum
Surge protection for supply voltage
Electronic (35 V, 0.5 s)
Polarity reversal protection for supply voltage
Via the system in which the Smart Element is used
Protection
External fusing via the system in which the Smart Element is
used
Safe digital inputs
Number of inputs
8 (1-channel assignment)
4 (2-channel assignment)
Connection method
Push-in connection
Connection technology
3-wire
Description of the input
EN 61131-2, type 3
Nominal input voltage
24 V DC
Nominal input current
2.7 mA, typical
Input voltage range for “0” signal
-3 V DC ... 5 V DC
Input voltage range for “1” signal
11 V DC ... 30 V DC
Input current range for “0” signal
1.5 mA, maximum
Input current range for “1” signal
Minimum 2 mA
Input filter time
1.5 ms, 3 ms (default), 5 ms, 15 ms