Phoenix Contact Axioline F AXC 1050 Скачать руководство пользователя страница 1

User manual

Axioline F: 

Diagnostic registers, and 

error messges

Содержание Axioline F AXC 1050

Страница 1: ...User manual Axioline F Diagnostic registers and error messges ...

Страница 2: ...11 PHOENIX CONTACT 8663_en_03 Axioline F Diagnostic registers and error messges UM EN AXL F SYS DIAG 03 Modules of the Axioline F product group User manual Designation Revision Order No This manual is valid for ...

Страница 3: ...ANY Should you have any suggestions or recommendations for improvement of the contents and layout of our manuals please send your comments to tecdoc phoenixcontact com This is the safety alert symbol It is used to alert you to potential personal injury hazards Obey all safety measures that follow this symbol to avoid possible injury or death There are three different categories of personal injury ...

Страница 4: ...oducts in your specific application in particular with regard to observing the applicable standards and regulations All information made available in the technical data is supplied without any accompanying guarantee whether expressly mentioned implied or tacitly assumed In general the provisions of the current standard Terms and Conditions of Phoenix Contact apply exclusively in particular as conc...

Страница 5: ...tics via object 0018hex DiagState 10 1 3 Diagnostic registers of the local bus master 12 1 3 1 Diagnostic status register 12 1 3 2 Diagnostic parameter register 14 1 4 Diagnostics register of the AXC controller 15 1 5 Diagnostics register of the AXL F BK bus coupler 16 2 Error codes 17 2 1 Error codes for user errors 17 2 2 Error codes for bus diagnostics 22 2 3 Error codes when calling the PDI se...

Страница 6: ...UM EN AXL F SYS DIAG 6 PHOENIX CONTACT 8663_en_03 ...

Страница 7: ...e con nected I O device Extended diagnostics Some modules have extended diagnostics For example a short circuit or an overload of the sensor supply can be detected and reported If a short circuit occurs at an output some output modules can diagnose each channel individually Information about the supply volt age is also reported Information about I O errors is sent to the controller with precise de...

Страница 8: ...V1 1 The desired and actual configuration are different No local bus device connected The maximum number of local bus devices is exceeded Active Flashing green The station is ready for operation communication within the station is OK The data is not valid Valid data from the controller higher level net work is not available There is no fault in the module Active Force Flashing yellow Access from S...

Страница 9: ... green The device is ready for operation communication within the station is OK The data is not valid Valid data from the controller higher level net work is not available There is no fault in the module Device applica tion not active Flashing green yel low The device is ready for operation communication within the station is OK Output data cannot be output and or input data cannot be read There i...

Страница 10: ...or number Unique consecutive number since the last power up reset or the last reset of the diagnos tics counter 0 65535dec 2 Unsigned 8 1 Priority 00hex No error 01hex Error 02hex Warning 03hex Information 81hex Error eliminated 82hex Warning eliminated 83hex Information eliminated 3 Unsigned 8 1 Channel group mod ule Channel group or module where the error oc curred Additional information under A...

Страница 11: ...sk of error A warning does not require action to be taken in the device 03hex Low Information message notification General operating message 10000 operating hours have elapsed General operating message 10000 oper ating hours have elapsed Diagnostic object 0018hex is implemented with a storage depth of 1 This means that A higher priority message overwrites a lower priority message Lower priority me...

Страница 12: ...tatus register Bit Designation Meaning 00 F_PW_BIT I O warning At least one device indicates an I O warning 01 F_PF_BIT I O error At least one device indicates an I O error 02 F_BUS_BIT Bus error A bus error occurred 03 F_CTRL_BIT Controller error The driver detected an internal error 04 Reserved 05 F_RUN_BIT Run Data cycles are being exchanged output data is enabled 06 F_ACTIVE_BIT Active Configu...

Страница 13: ...ndicated with BUS or CTRL will cause the bus to be disconnected The Run indicator bit is reset F_RUN_BIT 0 Further information on the error cause is provided by the two diagnostic parameter regis ters If several error bits are 1 at the same time the values in the parameter registers represent the error with the highest priority If there are I O errors PF at several devices the parameter registers ...

Страница 14: ...nal information on the status indicated in the diagnostic status register when the error bits specified above are set The diagnostic parameter register 1 contains the error code An overview of the error codes can be found in Section 2 Error codes The diagnostic parameter register 2 contains additional information For localized bus or I O errors this is the error location or the device number The e...

Страница 15: ...BOOL Bus error AXIO_DIAG_STATUS_REG_RUN BOOL Data transmission is active AXIO_DIAG_STATUS_REG_ACT BOOL Selected configuration is ready to operate AXIO_DIAG_STATUS_REG_RDY BOOL Axioline F local bus is ready for operation AXIO_DIAG_STATUS_REG_SYSFAIL BOOL The Axioline F local bus switches to the SYSFAIL state when the controller is in the STOP state or there is no pro gram present on it Table 1 6 Sy...

Страница 16: ...PROFINET SYS Yes AXL F BK ETH Ethernet Modbus registers Local bus diagnostics 7997 diagnostic status register 7998 diagnostic status register 1 7999 diagnostic status register 2 I O diagnostics 1801 1989 I O diagnostics of local bus devices DB EN AXL F BK ETH Yes AXL F BK EIP EtherNet IP Axioline F diagnostics object class code 67hex UM EN AXL F BK EIP OBJECTS Yes AXL F BK S3 Sercos Diagnostics ID...

Страница 17: ...ers is inconsistent with the ser vice The Parameter_Count parameter does not agree with the number of subsequent words Match the number of parame ters 0913 Code of failed service The service called is not supported Use a service that is sup ported 0917 Code of failed service Service decoding failed Restart the device If the problem still occurs please contact Phoenix Contact 0918 Code of the unkno...

Страница 18: ...eady 0800 Active Fail Communication abort in Active 1000 Param Ready Fail Communication abort in Ready parameter 2000 Run Fail Process data traffic with subsystem 4000 Force Fail Application timeout for all devices 8000 Force Mode Fail Communication abort in Force_Mode Set the local bus master to the required state 0A03 Memory problem e g buffer too small Restart the device If the problem still oc...

Страница 19: ...could be assigned Create the configuration frame 0A70 A reserved bit has been set in the Diag_Info attribute Check the parameters 0A73 Device number Device present with a chip version in the local bus that is not supported Replace the device 0A74 Device number Device of a manufacturer that is not supported present in the local bus Replace the device 0A75 Device number Device is indicating a seriou...

Страница 20: ...does not support the specified cycle time Select a different cycle time or a different device 0A92 Device number Device was selected for synchronization but does not support the specified value for Input_Delay Select a different value for In put_Delay or a different de vice 0A93 Device number Device was selected for synchronization but does not support the specified value for Output_Delay Select a...

Страница 21: ... 0B07 Object does not exist 0B0C A hardware or firmware error occurred OBC1 Supply voltage not available for the local bus Too many devices connected or the higher level power supply unit is too weak Use a suitable power supply unit Check the power consump tion of the devices if re quired use a power module for communications power or install a further Axioline F sta tion 0BDE Synchronization fail...

Страница 22: ... additional device was added at the end of the physi cal bus structure after the configuration frame was con nected 0C11 The module is not located in the configured slot An active device was inserted at the different location of the physical bus structure after the configuration frame was connected 0C12 The module is accessible but was not put into operation due to missing parameters An active dev...

Страница 23: ...ional code Meaning Remedy 2 Error in the communication relationship Check the call 1 Unable to access the object Possible causes Module not present Incorrect module number 0 Other error 5 Faulty service Check the call 1 The current object state prevents the service from being executed 2 Problem with the PDU size Permissible length exceeded Object cannot be read completely 3 The service cannot be e...

Страница 24: ...ddress Check the call 5 Inconsistent object attributes 6 The service used cannot be applied to this ob ject 7 Object does not exist 8 Type conflict A Data not ready at present 0 Other error 8 0 xx30 A reserved bit or reserved code was used during parameterization xx Number of the affected elements 30 Value is out of range Check the parameterization 1 Error writing the object Check the call Error r...

Страница 25: ...If the problem still occurs please contact Phoenix Contact 11 Device not accessible bus error Check the bus configuration 12 Device cannot be reached timeout Check the device 13 Device not accessible because it was removed Check the bus configuration 21 Invalid device number Invalid slot number Value is 0 or larger than the maximum number of devices Check the call 22 Invalid device number Slot is ...

Страница 26: ... service cannot be executed at present 0022 Service cannot be executed in current device state device control 0023 Service cannot be executed at present as no object dictionary is available 0030 Value range of a parameter out of range 0031 Parameter value too large 0032 Parameter value too small 0040 Collision with other values 0041 Communication object cannot be mapped to the process data 0042 Pr...

Страница 27: ...ceived than specified in the last segment 00A8 Error reading the file if file system is available 00A9 Segment number invalid or duplicated segment ignored 00B1 The password cannot be replaced deleted 00B2 The password cannot be added too many passwords 00B3 The password cannot be assigned for the desired type of access Table 2 4 Additional codes Additional code hex Meaning ...

Страница 28: ...put Sensor supply overload for the inputs 2344 Overload at an output Short circuit overload of an output 2345 Sensor supply overload 3000 Voltage 3300 Output voltage Short circuit or overload at the output 3400 I O supply voltage failure Check the I O supply 3412 Sensor supply not present I O supply voltage failure 3422 Actuator supply not present 4000 Temperature 5000 Device hardware 5112 Faulty ...

Страница 29: ...the parameterization of the specified device 7000 Additional modules 7300 Encoder error Check the encoder 7305 Encoder error Check the encoder 7610 Receive buffer full Read the receive buffer 7611 Transmit buffer full Check the handshake 7620 EPROM device error Restart the device Replace the device if the error still occurs 7710 Open circuit at sensor cable Remove the open circuit Open circuit 800...

Страница 30: ... system for the following aspects Missing or incorrect shielding of the bus line con nector Missing or incorrect grounding missing or incorrect equipotential bonding Faulty connections in the connector Voltage dips on the power supply A021 Lower level bus timeout A022 Lower level bus multiple transmission errors A023 Lower level bus I O data communication error A024 Lower level bus management data...

Отзывы: