Firmware services
All implemented firmware services of the Axioline F local bus can be removed using the AX-
_CONTROL function block, with the following exceptions:
–
PDI_READ_OBJECT (0041
hex
)
–
PDI_WRITE_OBJECT (0042
hex
)
The PDI_READ and PDI_WRITE function blocks are available for these services (see
7.13
Function block for UTC
The GET_UTC_TIMESTAMP function block enables you to query the coordinated universal
time UTC.
Function block
Figure 7-26
GET_UTC_TIMESTAMP function block
Input parameters
For information on the firmware error messages and diagnostic registers of the Axioline F
local bus master, refer to the UM EN AXL F SYS DIAG user manual.
The function is available for the AXC 1050 (XC) with a firmware version
≥
3.00 from
AUTOMATIONWORX Software Suite 2017 Version 1.84 and later.
Table 7-13
ENABLE input of the GET_UTC_TIMESTAMP function block
Name
Data type
Description
ENABLE
BOOL
The function block is activated on a positive
edge at this input. Every cycle, the function
block provides the updated UTC. The function
block remains active while the input has the
TRUE status.