The PLOS-CM-KNX is a low profile recessed flush mount 360º ceiling 

mount sensors that combines motion detection (PIR) and ambient light 

level detection (PE) in one device. The sensor is powered directly by the 

KNX network that is running between the KNX devices, eliminating the 

need for additional network field wiring or network power cables. The 

sensor can only be used when connected to a KNX network.
In applications such as office buildings, lecture theatres, and homes, 

the PLOS-CM-KNX multi function sensor can be utilised to detect 

different levels of motion and switch on the lights. The sensor can detect 

movements over a 7.4m x 5.6m area at a mounting height of 2.4m. 

When an area is unoccupied the sensor can detect this and the lights 

can be automatically dimmed or switched off to provide energy savings. 

The unit also incorporates a segmented click-up bezel surrounding the 

motion sensor element. This enables a portion of the sensing field to be 

readily masked to prevent nuisance detection from adjacent doorways 

or corridors. In situations where it is critical to maintain precise lighting 

control for individual workspaces, such as an office workstation or 

even air traffic control centers, the PLOS-CM-KNX facilitates light 

compensation. 

Instructions

This unit is for indoor use only. It is designed for installation in a 64mm 

diameter hole where the ceiling void is at least 40mm deep. Select an 

appropriate dry indoor mounting location, as detailed in the location 

guidelines on the following pages. Note that the product has two 

functions, and the optimum mounting location for each individual function 

may conflict with each other, and may require use of multiple sensors.

PLOS-CM-KNX

Ceiling Mount Universal Sensor

INSTALLATION MANUAL

Содержание PLOS-CM-KNX

Страница 1: ...mmedorswitchedofftoprovideenergysavings Theunitalsoincorporatesasegmentedclick upbezelsurroundingthe motionsensorelement Thisenablesaportionofthesensingfieldtobe readilymaskedtopreventnuisancedetectionfromadjacentdoorways orcorridors Insituationswhereitiscriticaltomaintainpreciselighting control for individual workspaces such as an office workstation or even air traffic control centers the PLOS CM...

Страница 2: ...7 For programming instructions refer to the Philips LightMaster Commisiioning guide PIR sensor Click up bezel for motion shield KNX programming push button and LED Light level sensor Data Cable Termination KNX TP1 cable termination 1 Strip off between 25 40mm of outer jacket 2 Cut shield synthetic foil and tracer flush to the outer jacket 3 Cut yellow white pair if unused insulate ends 4 Applyalay...

Страница 3: ...X has a built in pull up mask that can be rotated to remove 120 scanning range from thesensor Thisfeaturecanbeusedinsituationwhen a section of the motion detection zone needs to be blocked out When mounting the sensors in a single office the mask can be used to block out motion that would be detected in the corridor causing false triggering of the sensor and then turning on the lightingunnecessary...

Страница 4: ...x 250mm Detection zones 64 LED activation indicator Sensor Quad element pyro electric PE Cell Range 5 lux to 5000 lux reflected Automatic Daylight Harvesting mode Controls KNX Programming switch LED Control Bus KNX TP1 21 30Vdc KNX power Consumption Power Consumption max 10mA Terminals Wago 243 Red Grey 0 6 0 8mm wire diameter Single Core KNX Cable Environment 5º to 45ºC operating ambient temperat...

Отзывы: