E6 Series
Commercial Emergency Lighting
Page 1 of 2
Job Information
Type:
Job Name:
Cat. No.:
Notes:
Features
Illumination:
Illumination
is provided by two fully-
adjustable polycarbonate lamp
heads. Each lamp head utilizes
a high-performance parabolic
reflector in conjunction with a
6 VDC, 5.4 W T-5 wedge base
tungsten lamp. High-impact
acrylic refractors minimize
glare and maximize optic
control.
Housing:
Constructed of
impact resistant , UL 94 V-0,
5 VA thermoplastic, completely
self-contained. White housing
is standard, with an optional
black housing available.
Operating Temperature
Range:
Damp Location
68°F (20°C) to 104°F (40°C)
Diagnostic Electronics
(standard):
120/277 VAC
dual voltage input with surge-
protected, solid-state charging
circuitry provides for a reliable
charging system. Charging
system is complete with
low voltage disconnect, AC
lockout, brownout protection,
AC indicator lamp and test
switch.
Self-Testing Diagnostics
(optional):
Continuously
monitors the critical functions
of the equipment, including:
battery disconnect, battery
failure, charger failure,
transformer failure and lamp
failure. Self-Testing routine
performs a one-minute test
every 30 days, a 30-minute
test on the 6th month and a
90-minute test annually.
Electrical Specifications:
0.045 A (120 VAC)
0.020 A (277 VAC)
Code Compliance
UL 924 and UL damp location
listed. NFPA 101, NEC, BOCA,
OSHA and IBC illumination
standards.
Warranty
Three year full electronics
warranty. One year full plus
four year prorated battery
warranty.
E611
16.0"
(40.6 cm)
5.0"
(12.7 cm)
11.87"
(30.15 cm)