Parameter ranges
#
PARAMETERS
RANGE
MAIN
o
F
o
C
0
Memory Protect
ON / OFF
1
Temp Set (Start P-Band1)
32.0 to 110.0
0.0 to 43.3
2
Stage 1 Min Vent
Min Idle (parm #21) – 99
3
Stage 2 Min Vent
Min Idle (parm #22) – 99
DIFFERENTIAL
4
Stage 1 Off-Set-Back
IDLE, -20.0 to 0.0
IDLE, -11.1 to
0.0
5
Stage 1 P-Band1
0.0 to 16.0
0.0 to 8.9
6
Stage 2 Off-Set-Back
IDLE, -20.0 to 0.0
IDLE, -11.1 to
0.0
7
Stage 2 Start P-Band2
-10.0 to 15.0, OFF
-5.5 to 8.4, OFF
8
Stage 2 P-Band2
0.0 to 16.0
0.0 to 8.9
9
Stage 3 Turn On
-10.0 to 15.0, OFF
-5.5 to 8.4, OFF
10 Not
Applicable
11 Not
Applicable
12
Low Temp Alarm
OFF, -36.0 to 0.0
OFF, -20.0 to
0.0
13
High Temp Alarm
0.0 to 36.0, OFF
0.0 to 20.0, OFF
GENERAL
14
Low Power Alarm
ON / OFF
15
Alarm Display Latching
ON / OFF
16
Ventilation
ON / OFF
SETUP
17 Units
o
F or
o
C
o
F /
o
C
18
Stage 3 Operation
HEAT / COOL
19 Not
Applicable
20 Not
Applicable
21
Stage 1 Minimum Idle
0 to 99
22
Stage 2 Minimum Idle
0 to 99
23
Hysteresis
0.5 to 2.5
0.3 to 1.4
24
Stage 1 P.F. Compensation
0.5 to 2.5
25
Stage 2 P.F. Compensation
0.5 to 2.5
Table 1
: Adjustable ranges of parameters
10245506