Procedure
1. Take the settings for the motor protection switch from the following table.
2. Take into consideration that certain operating conditions (for example, cold vacuum pump start)
can cause short-term increases in current consumption.
3. Set the desired value on the motor protection switch.
Voltage [V]
Frequency [Hz]
Motor rating [kW]
I
N
[A]
I
max
[A]
190 – 200
50
5.5
24.2
204
220 – 230
50
5.5
20.9
176
380 – 400
50
5.5
12.1
102
208
60
6.6
25.6
213
220
60
6.6
24.2
201
230
60
6.6
24.2
201
440
60
6.6
12.1
101
460
60
6.6
12.1
101
Tbl. 6:
Motor protection switch settings for global motor Hena 201 R
Voltage [V]
Frequency [Hz]
Motor rating [kW]
I
N
[A]
I
max
[A]
200
50
5.5
25.6
241
346
50
5.5
14.8
140
220
60
6.6
24.2
221
380
60
6.6
14.0
128
Tbl. 7:
Motor protection switch settings for Asian motor Hena 201 R
Voltage [V]
Frequency [Hz]
Motor rating [kW]
I
N
[A]
I
max
[A]
190 – 200
50
7.5
32.6
297
220 – 230
50
7.5
28.2
257
380 – 400
50
7.5
16.3
149
208
60
9.2
33.0
314
220
60
9.2
32.2
306
230
60
9.2
32.0
304
440
60
9.2
16.1
153
460
60
9.2
16.0
152
Tbl. 8:
Motor protection switch settings for global motor Hena 251 | Hena 301 R
Voltage [V]
Frequency [Hz]
Motor rating [kW]
I
N
[A]
I
max
[A]
200
50
7.5
38.5
351
346
50
7.5
22.2
202
220
60
9.2
36.3
345
380
60
9.2
21.0
200
Tbl. 9:
Motor protection switch settings for Asian motor Hena 251 | Hena 301 R
5.6.5 Frequency inverter for vacuum pumps with 3-phase motor
Rotary vane pumps with variable rotation speed can be operated within a mains frequency range of 35
to 60 Hz. Start-up is ramped (maximum run-up time: 30 s). Shutdown can take place immediately.
Installation
29/62
Содержание HENA 201 R
Страница 1: ...OPERATING INSTRUCTIONS EN Translation of the Original HENA 201 R 251 301 R Rotary vane pump...
Страница 19: ...Locking caps for vacuum and exhaust connection Operating instructions Product description 19 62...
Страница 62: ...Notizen Notes...
Страница 63: ......
Страница 64: ...PD0087 ed D Date 2007 P N PD0087BEN...