Electrical connection
13.3.
Illustration 8 - Terminal assignment
Connection No. X1
Function
1
Operating voltage light + (24V)
2
Operating voltage light – (GND)
3
Operating monitoring circuit
+ (24V)
4
Operating monitoring circuit
– (GND)
5
Fault indicator output S1 (NC)
6
Fault indicator output S1 (NC)
7
Fault indicator output S2 (NO)
8
Fault indicator output S2 (NO)
Table 4 - Assignment of the terminal clamps (X1)
Settings
13.4.
DIP switch
Switch No.
Switch position
OFF
Switch position
ON
Sector configuration
1
Sector 1 deactivated
Sector 1 active
2
Sector 2 deactivated
Sector 2 active
3
Sector 3 deactivated
Sector 3 active
4
Sector 4 deactivated
Sector 4 active
Operation modes
5 – 6
OFF – OFF
Rotating light 150 rpm
ON – OFF
Blinking mode 1.5 Hz, 50% Duty Cycle
OFF – ON
Double flash 1 Hz
ON – ON
7
Automatic switchover to night mode
with reduced LED brightness permitted
Always on day mode with maximum
permissible LED brightness
8
reserved
Table 5 - DIP switch coding
Alarm output S1 (NC)
Alarm output S2 (NO)
Operational voltage
Flash monitoring
Operational voltage
Flashing light
DIP switch
Configuration of operating mode / sector configuration
085501100
page
11 /16
30401 – 004-2