11U – Location ID
Range:
0 - 65535
Default:
0
Description:
Sets the soft starter's unique location ID.
10.16 12 Pump Input Configuration
NOTE
The parameters in this group are only active if a smart card is installed.
12A – Auto-Reset Count
Range:
0 – 5
Default:
0
Description:
Sets how many times the soft starter will auto-reset, if it continues to
trip.
The reset counter increases by one each time the soft starter auto-
resets, and resets after a successful start.
Setting 12A to zero disables auto-reset.
NOTE
Auto-reset will reset trips from any source, not just from the smart card.
12B – Auto-Reset Delay
Range:
0:05 - 15:00 (minutes:seconds)
Default:
5 seconds
Description:
Sets a delay before the VersiStart p III will auto-reset a trip.
12C – Pressure Sensor Type
Options:
None (default)
Switch
Analog
Description:
Selects which type of sensor is associated with the pressure sensor
input on the smart card.
12D – Pressure Units
Options:
Bar
kPa (default)
Psi
Description:
Selects which units the sensor will use to report the measured
pressure.
12E – Pressure at 4 mA
Range:
0 – 5000
Default:
0
Description:
Calibrates the soft starter to the 4 mA (0%) level of the pressure
sensor input.