VersiStart p III
Motor Thermistor
Motor thermistors can be connected directly to the VersiStart P III. The soft starter
will trip when the resistance of the thermistor circuit exceeds approximately
3.6 k
Ω
or falls below 20
Ω
.
The thermistors must be wired in series. The thermistor circuit should be run in
screened cable and must be electrically isolated from earth and all other power and
control circuits.
NOTE
The thermistor input is disabled by default, but activates automatically when
a thermistor is detected. If thermistors have previously been connected to
the VersiStart p III but are no longer required, use the Thermistor Reset
function to disable the thermistor. Thermistor Reset is accessed via the
Setup Tools.
Start/Stop
The VersiStart P requires two-wire control.
A
B
17622.
A
A
Reset
B
Start/Stop
NOTE
The VersiStart p III will only accept commands from the control inputs if
parameter 1A
Command Source
is set to Digital Input.
Reset/Starter Disable
The reset input (10, 11) is normally closed by default. The VersiStart p III will not
perform a start if the reset input is open. The display will show "Not Ready".
If the reset input opens while the VersiStart p III is running, the starter will remove
power and allow the motor to coast to stop.
NOTE
The reset input can be configured for normally closed operation. Use
parameter 7I
Reset/Enable Logic
.
Programmable Inputs
The programmable inputs (13, 14 and 13, 15) allow external equipment to control
the starter.
The operation of the programmable inputs is controlled by parameters 7A ~ 7H.
USB Port
The USB port can be used to upload a configuration file, or download parameter
settings and event log information from the starter. Refer to
USB Save & Load
on
page 36 for details.