VersiStart i II 

 

 

 
 

4.4

 

Outputs 

4.4.1

 

Main Contactor Output 
The Main Contactor output (terminals 13, 14) closes as soon as the soft starter receives a start command and 

remains closed while the soft starter is controlling the motor (until the motor starts a coast to stop, or until the 

end of a soft stop).  The Main Contactor output will also open if the soft starter trips. 
The Main Contactor output can be used to directly control a main contactor coil. 

 

4.4.2

 

Programmable Output 
The programmable output relay (terminals 23, 24) can be used to signal either trip or run status.  This relay is 

normally open. 
Trip: 

The relay closes when the VersiStart i II trips.  The relay can be used to operate the shunt-trip mechanism of 

an upstream circuit breaker (in order to isolate the motor branch circuit), or to signal the trip to an automation 

system or externally.  The relay will open when the trip is reset. 
Run: 

The relay operates when the soft start is complete, the bypass relays are closed and full voltage is being 

applied to the motor.  The relay can be used to operate a contactor for power factor correction capacitors, or to 

signal soft starter run status to an automation system. 

 

4.5

 

Electrical Schematics 

Soft starter installed with a system protection 

circuit breaker complete with a shunt trip device 

Soft starter installed with a system protection circuit breaker 

and main contactor 

6/T3

4/T2

2/T1

5/L3

3/L2

1/L1

13

14

M

23

24

K1

 

6/T3

4/T2

2/T1

5/L3

3/L2

1/L1

13

14

M

K1

K1

23

24

 

 

M 

Motor (three phase) 

K1 

Main contactor 

13, 14 

Main contactor output 

23, 24 

Programmable output (set to Trip) 

 

Содержание VersiStart i II

Страница 1: ...ion 4 3 1 Dimensions and Weights 4 3 2 Physical Installation 4 4 Electrical Installation 5 4 1 Power Terminations 5 4 2 Control Voltages 5 4 3 Control Circuits 6 4 4 Outputs 7 4 5 Electrical Schematic...

Страница 2: ...Only a qualified electrician should carry out the electrical installation Improper installation of the motor or the VersiStart i II may cause equipment failure serious injury or death Follow this manu...

Страница 3: ...and 2014 35 EU Low voltage directive is not proved The devices of the VersiStart i II series are electrical equipment that is used in industrial electrical power installations They are designed for a...

Страница 4: ...VS i II 170 200 160 240 216 214 114 5 51 6 5 VS i II 200 7 87 6 30 9 44 8 50 8 43 4 5 2 0 14 33 3 2 Physical Installation 1 2 3 4 08241 D VS i II 018 VS i II 100 Allow 100 mm 3 9 inch between soft st...

Страница 5: ...428 A 6 mm 0 24 inch Torx T20 3 Nm 2 2 ft lb Torx T20 4 Nm 2 9 ft lb n a n a 7 mm 3 Nm 2 2 ft lb 7 mm 4 Nm 2 9 ft lb n a 3 5 mm 0 5 Nm max 4 4 in lb max 4 2 Control Voltages VersiStart i II soft start...

Страница 6: ...trol input terminals 01 02 Two wire control Three wire control 110 240 VAC 24 VAC VDC A3 A1 A2 01 02 A3 A1 A2 01 02 1 1 03241 D A3 A1 A2 01 02 A3 A1 A2 01 02 2 3 2 3 03242 E 380 440 VAC Start stop To...

Страница 7: ...shunt trip mechanism of an upstream circuit breaker in order to isolate the motor branch circuit or to signal the trip to an automation system or externally The relay will open when the trip is reset...

Страница 8: ...the motor during the soft start Current Time Motor Trip Class 08246 A Select the trip class for motor overload protection The trip class reflects the maximum time in seconds that the motor can run at...

Страница 9: ...ed time E Current Time Auxiliary Relay Function 08250 A Select the function of the soft starter s programmable output terminals 23 24 When set to Run the relay will operate when the soft start is comp...

Страница 10: ...thermistor connection B4 B5 Allow motor to cool x 5 Current imbalance Check for mains supply or line current imbalance L1 L2 L3 x 6 Supply Frequency Check mains voltage is available and supply freque...

Страница 11: ...and low frequency limits both apply with no time delay A supply frequency trip will also occur if all three input phases are lost while the soft starter is running all three input phases fall below 12...

Страница 12: ...n Modules VersiStart i II soft starters support network communication via easy to install communications modules Each soft starter can support one communications module at a time Available protocols E...

Страница 13: ...0 VAC and 5 6 k 24 VAC VDC Outputs Main contactor relay terminals 13 14 Normally open 6 A 30 VDC 6 A 250 VAC resistive Programmable relay terminals 23 24 Normally open 6 A 30 VDC 6 A 250 VAC resistive...

Страница 14: ...ics and distortion IEC61000 2 4 Class 3 EN IEC61800 3 Short Circuit Rated short circuit current VS i II 018 to VS i II 048 5 kA 1 Rated short circuit current VS i II 060 to VS i II 200 10 kA 1 1 These...

Страница 15: ...C 50 C VS i II 018 18 A 17 A 17 A 15 A VS i II 034 34 A 32 A 30 A 28 A VS i II 042 42 A 40 A 36 A 33 A VS i II 048 48 A 44 A 40 A 36 A VS i II 060 60 A 55 A 49 A 45 A AC53b 4 6 594 1000 metres AC53b 4...

Страница 16: ...URD30xxxA0160 A070URD30xxx0160 170M 1318 160 FEE VS i II 048 15000 6 6URD30xxxA0160 A070URD30xxx0160 170M 1318 180 FM VS i II 060 18000 6 6URD30xxxA0160 A070URD30xxx0160 170M 1319 180 FM VS i II 075 5...

Отзывы: