background image

 

 

VersiStart i II 

11 

 

 

 
 

6.3.2

 

Motor Overload Protection 
The VersiStart i II will trip on motor overload if it calculates that the motor has been running above its operating 

range for longer than the time selected in the Motor Trip Class setting.  Motor Trip Class should be set to 

match the motor's locked rotor time.  If this information is not available from the motor datasheet, use the 

default setting (Motor Trip Class = 10).  Using a higher setting can damage the motor. 

 

NOTE 

Motor overload protection does not protect the soft starter, and does not protect the motor from short 

circuit.    

 

6.3.3

 

Current Imbalance Protection 
The VersiStart i II will trip on current imbalance if the highest and lowest currents on the three phases vary by 

an average of 30% for more than 3 seconds.  Current imbalance protection is not adjustable, and is only active 

when the average motor current is 50% or more of the programmed motor FLC.   
If the soft starter frequently trips on current imbalance: 

 

check that there is no imbalance on the mains voltage (on the input side of the soft starter) 

 

insulation test the motor 

 

move all input cables over one position (move L1 cable to L2, move L2 cable to L3, move L3 cable to 

L1) to rule out a cabling fault 

 

6.3.4

 

Supply Frequency Protection 
The soft starter will trip on supply frequency if the frequency rises above 72 Hz or falls below 40 Hz for more 

than five seconds while the soft starter is running.  These trip points are not adjustable.   
In pre-start, starting and stopping modes the high and low frequency limits both apply with no time delay. 
A supply frequency trip will also occur if: 

 

all three input phases are lost while the soft starter is running 

 

all three input phases fall below 120 VAC at start or while the soft starter is running 

 

the line contactor opens while running 

 

6.3.5

 

Bypass Overload Protection 
Bypass overload protection protects the soft starter from severe operating overloads while running.  The 

protection is not adjustable and has two components: 

 

The soft starter will trip if it detects overcurrent at 600% of the programmed motor full load current. 

 

The soft starter models the temperature of the internal bypass relays and will trip if the temperature 

exceeds the safe operating level. 

If the trip occurs frequently, this indicates that the soft starter has not been selected correctly for the application. 

 

6.4

 

Reset 

Trips can be cleared by pressing the Reset button on the soft starter, sending a Reset command from the serial 

communications network, or by switching the control inputs. 
To clear a trip via the control inputs, the soft starter requires a closed to open transition on the stop input (02). 

 

In three-wire control, use the external stop button to momentarily open the stop input (open A1-02). 

 

In two-wire control, if the soft starter tripped with a start signal present, remove the start signal (open 

A1 to 01, 02). 

 

 

In two wire control, if the VersiStart i II tripped with no start signal present (eg VersiStart i II motor 

thermistor trip), apply then remove the start signal (close then reopen A1 to 01, 02). 

 

The Reset button is located on the front of the unit, above the adjustment switches. 

 

The soft starter will trip again immediately if the cause of the trip still exists. 

 

Содержание VersiStart i II

Страница 1: ...ion 4 3 1 Dimensions and Weights 4 3 2 Physical Installation 4 4 Electrical Installation 5 4 1 Power Terminations 5 4 2 Control Voltages 5 4 3 Control Circuits 6 4 4 Outputs 7 4 5 Electrical Schematic...

Страница 2: ...Only a qualified electrician should carry out the electrical installation Improper installation of the motor or the VersiStart i II may cause equipment failure serious injury or death Follow this manu...

Страница 3: ...and 2014 35 EU Low voltage directive is not proved The devices of the VersiStart i II series are electrical equipment that is used in industrial electrical power installations They are designed for a...

Страница 4: ...VS i II 170 200 160 240 216 214 114 5 51 6 5 VS i II 200 7 87 6 30 9 44 8 50 8 43 4 5 2 0 14 33 3 2 Physical Installation 1 2 3 4 08241 D VS i II 018 VS i II 100 Allow 100 mm 3 9 inch between soft st...

Страница 5: ...428 A 6 mm 0 24 inch Torx T20 3 Nm 2 2 ft lb Torx T20 4 Nm 2 9 ft lb n a n a 7 mm 3 Nm 2 2 ft lb 7 mm 4 Nm 2 9 ft lb n a 3 5 mm 0 5 Nm max 4 4 in lb max 4 2 Control Voltages VersiStart i II soft start...

Страница 6: ...trol input terminals 01 02 Two wire control Three wire control 110 240 VAC 24 VAC VDC A3 A1 A2 01 02 A3 A1 A2 01 02 1 1 03241 D A3 A1 A2 01 02 A3 A1 A2 01 02 2 3 2 3 03242 E 380 440 VAC Start stop To...

Страница 7: ...shunt trip mechanism of an upstream circuit breaker in order to isolate the motor branch circuit or to signal the trip to an automation system or externally The relay will open when the trip is reset...

Страница 8: ...the motor during the soft start Current Time Motor Trip Class 08246 A Select the trip class for motor overload protection The trip class reflects the maximum time in seconds that the motor can run at...

Страница 9: ...ed time E Current Time Auxiliary Relay Function 08250 A Select the function of the soft starter s programmable output terminals 23 24 When set to Run the relay will operate when the soft start is comp...

Страница 10: ...thermistor connection B4 B5 Allow motor to cool x 5 Current imbalance Check for mains supply or line current imbalance L1 L2 L3 x 6 Supply Frequency Check mains voltage is available and supply freque...

Страница 11: ...and low frequency limits both apply with no time delay A supply frequency trip will also occur if all three input phases are lost while the soft starter is running all three input phases fall below 12...

Страница 12: ...n Modules VersiStart i II soft starters support network communication via easy to install communications modules Each soft starter can support one communications module at a time Available protocols E...

Страница 13: ...0 VAC and 5 6 k 24 VAC VDC Outputs Main contactor relay terminals 13 14 Normally open 6 A 30 VDC 6 A 250 VAC resistive Programmable relay terminals 23 24 Normally open 6 A 30 VDC 6 A 250 VAC resistive...

Страница 14: ...ics and distortion IEC61000 2 4 Class 3 EN IEC61800 3 Short Circuit Rated short circuit current VS i II 018 to VS i II 048 5 kA 1 Rated short circuit current VS i II 060 to VS i II 200 10 kA 1 1 These...

Страница 15: ...C 50 C VS i II 018 18 A 17 A 17 A 15 A VS i II 034 34 A 32 A 30 A 28 A VS i II 042 42 A 40 A 36 A 33 A VS i II 048 48 A 44 A 40 A 36 A VS i II 060 60 A 55 A 49 A 45 A AC53b 4 6 594 1000 metres AC53b 4...

Страница 16: ...URD30xxxA0160 A070URD30xxx0160 170M 1318 160 FEE VS i II 048 15000 6 6URD30xxxA0160 A070URD30xxx0160 170M 1318 180 FM VS i II 060 18000 6 6URD30xxxA0160 A070URD30xxx0160 170M 1319 180 FM VS i II 075 5...

Отзывы: