12.4 Possible fault indications during commissioning

During  commissioning,  and  in  normal  operation  too,  fault  indications  can  occur.  The  following 
explanation is to give you assistance in the localization and correction of faults.

Fault 
indication on 
LED „Ready“,

 

„(V9)“

Fault

Possible cause

Fault correction

 Flashing 1x

No motor standstill 
during max. braking 
time

Braking current adjusted to a 
too small value.

Adjust braking current to a 
higher value.

Too large centrifugal mass.

Use VBMS with longer max. 
braking time.

Terminal „6T3“ „(T3)“ is not 
connected and the motor is not 
suplied with current for a period 
of 1,5s prior to the standstill.

If possible, connect 6T3 (T3) or 
adjust the braking current to a 
slightly lower value.

Standstill threshold is not 
adapted.

Adapt standstill threshold with 
„n0“.

Flashing 2x

Adjusted braking 
current was not 
reached.

Interruption in the braking 
circuit. Possibly the motor is 
started with star-delta 
connection.

Check circuit. Possibly the star 
contactor has to be closed 
during braking.

The resistance of the motor 
winding is too high for the 
adjusted braking current.

Turn braking current back so 
that the fault does not occur 
any more.

Flashing 3x

VBMS is 
overloaded. 

 

Braking frequency is 
too high.

The specified max. braking 
frequency is exceeded.

Reduce braking current or 
braking frequency. 
During commissioning, 

 

4 braking operations in 
succession can be initiated 
without an overload being 
indicated.

Flashing 4x

Contacts of motor 
contactor are 
charred/short-
circuited.

Starting current of the motor is 
too high (high-inertia starting, 
blocked motor).

Send device for repair.

Motor with too high power 
rating was connected.

Send device for repair.

Flashing 5x

3x in succession no 
standstill detected

Braking current adjusted to a 
too small value.

Adjust braking current to higher 
value.

Centrifugal mass is too large.

Use braking device with longer 
max. braking time or higher 
rated device current.

Standstill threshold is not 
adapted.

Adapt standstill threshold with 
„n0“.

Flashing 6x

Program error

Program crash

Send device for repair.

Содержание 2C000.23020

Страница 1: ...e l e c t r o n i c Quality is our Drive Combined Motor Start and Braking Device VBMS Assembly and Commissioning Instructions...

Страница 2: ...inputs 9 10 Potentiometers 9 11 Technical data 10 11 1 Environmental conditions 10 12 Commissioning 11 12 1 Mounting instructions 11 12 2 Connection 11 12 3 Parameter settings 12 12 4 Possible fault...

Страница 3: ...e this sign always make sure that the device is de energized and secured against unintentional energizing These commissioning instructions were prepared with great care Nevertheless PETER electronic G...

Страница 4: ...d the trade associations apply in Germany The user must ensure that the drive turns into a safe operating state following a device failure in the event of maloperation or if the control unit has faile...

Страница 5: ...only a few elements motor contactor and DC brake in a single device suitable for all asynchronous motors controlled bei microcontroller easy mounting also for retrofitting into existing plants motor...

Страница 6: ...lowing EU directives 2014 30 EU 2014 35 EU 2011 65 EU This EC Declaration of Conformity is no longer valid if the product is modified or changed without our agreement This declaration is issued under...

Страница 7: ...ply unit Braking relay OFF Motor contactor ON Controller Pulse stage I n0 Motor contactor Braking relay 24VR Motor contactor Braking relay Remanence voltage X8 X7 X6 X5 X4 X3 Current detection X1 X2 1...

Страница 8: ...nt off approx 1 5s after a motor standstill has been detected To be able to adapt the device to a variety of motors it is possible to adjust the standstill threshold via the potentiometer n0 Faults th...

Страница 9: ...Flashing 3x repeatedly with a short pause Braking frequency too high Fault can only be reset by discon necting the device for 5s from the mains voltage motor contactor is inter locked Flashing 4x rep...

Страница 10: ...X1 X2 Starting contact Connection of an ON button normally open contact X3 X4 X5 X6 X7 X8 Braking contact Connection of an OFF button normally closed contact I Adjusting the braking current The braki...

Страница 11: ...160 IEC 38 3x 380 415V 10 3x 200 240V 10 AC 3 Rated operational power 2 2kW 1 5kW AC 3 Rated operational power on IE3 Motor 1 5kW 1 1kW Conventional Thermal current Ith Ie 16A Braking current 2 20A ma...

Страница 12: ...without being exposed to contamination by water oil carbon deposits dust etc Warning Make sure that a minimum distance to adjoining devices is kept Above and underneath the housing a minimum distance...

Страница 13: ...sary heating of the power semiconductors and motor This is especially important in the case of high switching frequencies We recommend to limit the max braking current to 2 5 times the rated motor cur...

Страница 14: ...lta connection Check circuit Possibly the star contactor has to be closed during braking The resistance of the motor winding is too high for the adjusted braking current Turn braking current back so t...

Страница 15: ...current has to be at least 2 5 times as high as the rated motor current in order to achieve a sufficiently high braking torque If special applications require more precise calculations the following...

Страница 16: ...fter a short circuit the braking device is allowed to be inoperative 2 Fusing according to allocation type 2 DIN EN 60947 4 2 After a short circuit the braking device must be suitable for further use...

Страница 17: ...fuse gL please refer to table 2 column 3 To protect the semiconductors it is necessary to select gR fuses featuring cutoff I t values of the ranges indicated in table 2 column 4 In this connection the...

Страница 18: ...ver the device needs a recovery time of 15 minutes cyclicduration factor r c d f tB cycletime x 100 tB Braking time Cycle time Braking time Non braking time Braking current Braking time Braking freque...

Страница 19: ...18 VBMS 14 Dimensional drawings All dimensions in mm 100 120 73...

Страница 20: ...4T2 6T3 1L1 3L2 5L3 Control with switch PE L1 L2 L3 F1 X8 X3 X4 X5 X6 X7 X2 X1 Switch closed operation open braking OFF Braking current Standstil adjustment 5L3 5L3 5L3 3L2 1L1 5L3 Connection with mo...