Task 3. Provisioning the sensor on the radio network
1.
Provision the sensor to join the gateway using the installation app
Refer to
User guide
–
IK220 installation kit
for detailed instructions. A summary of the steps is given
below
2.
Record the installation location, sensor ID, MAC address of the sensor, and power module serial
number.
Task 4. Completing sensor installation
In the installation app software on the Installation tab:
1.
Press the Start button. Wait for an ultrasonic waveform to download from the sensor.
Note:
Waveforms are automatically downloaded every 10 seconds. When a new waveform
arrives, the lines briefly become thicker.
2.
Check the quality of the waveform. The first one or two reflections must be well defined above the
noise. Only one reflection is needed to calculate a thickness.
If the signal is poor, loosen the strap by
unscrewing one of the worm-screws. Move the sensor and strap to a slightly different position then
follow steps 10 to 12 from task 1 to reinstall sensor in the new position. Once the sensor is safely
reinstalled on the pipe, wait 20 seconds before assessing the waveform quality for the new location
.
1. Enter network
ID and Join Key
2. Click Provision
3. Check the network ID of the gateway
is visible in the network discovery list