Honeywell v12 & v48 Keyswitch wiring & programming RDC_3142_E_TA
Honeywell V12 & V48 Alarm Panel
Keyswitch wiring
Keyswitch programming
NB: V48v4.1+ DO NOT: Zone double for keyswitch zone
Keyswitch a zone on any expander.
Background: There are three (3) Outputs available.
Outputs are
‘Open Collector’ @50mA switching negative - for heavier loads a relay must be used.
Outputs can be used for e.g. Keyswitch, opening gates or doors etc.
Ensure there is a common negative between Permaconn and the device being switched.
The outputs can be Opened, Closed or Pulsed remotely using the Permaconn Atlas web portal.
The Pocket Secure App can only ‘Pulse’ the Outputs. A Pulse is approx 1sec.
These outputs when wired to a Keyswitch zone on the Alarm Panel can arm & disarm up to a
maximum of thr
ee (3) areas when using ‘Pocket Secure’ app.
Each area should be independently controlled using a separate Keyswitch zone.
Arm/Disarm reporting
MUST be Enabled
. Pocket Secure App requires this for its status notifications.
Test each Output by placing the +ve leg of a multi meter on the +ve terminal that supplies power to the
Permaconn, then place the -ve leg of a multi meter on the Output terminal you wish to test. Pulse the
selected Output the result should go from 0v DC to 12v DC for approx 1sec and back to 0vDC.
E.g. 1: Keyswitch wiring between Permaconn and Honeywell v12 / 48 Alarm Panel
single zone Not Using Zone Doubling
:
Fit EOL resistor in parallel with zone input, then install a wire between the PM45-4G output and the zone input.
The zone must then be programmed for ‘Momentary Keyswitch’ operation.
Example programming showing v48, Zone 8 as Keyswitch on a PM45v3 4G.
Zone
Com
+
-
Common -ve
Vista
12a
48a
2
k
Each area should be independently controlled using a separate Keyswitch zone.
Any zone can be used as a keyswitch zone.
Sends event (E409 U000 for Disarm) & (R409 U000 for Arm) for keyswitch.
Compatible with ‘Pocket Secure’ remote arming App, available on iTunes, Google Play and the Windows Phone Store.