Ensure the condenser airflow divider is
installed on the lower interior portion
of the door. This divider prevents direct
circulation of machine compartment
air. If missing, unit will run extremely
inefficiently and extreme high discharge
pressures and temperature which could
lead to compressor damage.
See Figure
6-6.
Figure 6-6. Condenser Airflow Divider
Figure 6-5.1. Evaporator Air Outlet Louvers
Figure 6-5.2. Evaporator Air Damper Outlet Openings