Perle IDPS-48-240-XT Скачать руководство пользователя страница 1

IDPS-48-240-XT Hardware Installation Guide  

 

Introduction 
This document contains instructions for the installation of a Perle IDPS-48-240-XT industrial-grade power supply.  

Package List 

 

 One IDPS-48-240-XT power 
supply 

 

This guide 

 

 

Connecting AC or DC Power to the IDPS 
1.  Prior to connection, verify that power is off to the AC or DC circuit that you are going to attach to the AC/DC 

input power supply. 

2.  Strip all wires 5mm (3/16

th

 inch). 

3.  Loosen the terminal screws for  (Ground), N(eutral) and L(ive-line). Insert wire-leads of appropriate type and 

wire size into each terminal.  

4.  Secure the wire-leads and tighten the terminals screws (0.5Nm-0.6Nm torque). 
5.  Ensure that only insulated wire extends from the terminal connectors. 
6.  Turn on power at source. 

Connecting DC Power to end devices 
1.  Prior to connection, ensure that power is turned off at source. 
2.  Strip both wires 5mm (3/16

th

 inch). 

3.  Loosen the terminal screws for +V and –V. Insert wire-leads into the power supply’s DC OUT terminal 

connector positive (+) and negative (-) terminal connector. 

4.  Secure the wire-leads and tighten terminals screws (0.5Nm-0.6Nm torque). 
5.  Ensure only insulated wire extends from the terminal connectors. 
6.  Connect the other end of the wire-leads to the INPUT DC terminal connectors on the end device. 
7.  Turn on power at source. 
8.  Check that the DC OK LED is On. 

 

 

 

 

Mounting the IDPS to a DIN-rail 

1.

 

The DIN-rail clip is integrated on the back of the IDPS. 

2.  Position the IDPS such that the top of the integrated DIN-rail opening fits into the slot on the top of the DIN-rail. 
3.  Press the IDPS towards the DIN-rail until it is vertical to the DIN-rail and the bottom snaps into the bottom DIN-

rail. The IDPS is now secured to the DIN-rail. 

4.  To release the IDPS from the DIN-rail, use a small flat edge screwdriver gently pry downwards on the Tab at 

the bottom of the IDPS until the IDPS is released from the DIN-rail. 

INPUT: 85–264 VAC or 120–370 VDC  
1 Input connections: 

AC Live terminal or DC(+) Terminal 
 

AC Neutral terminal or DC(-) Terminal 
 

 

 

Gnd  ( terminal) 
 

 

 

4 Output connections: 

DC OK (LED) 
Off – No power to the IDPS (check power 
connections and power source 
On – IDPS is receiving power 
 

5  

DC OUTPUT terminals (-v)(-v)(+v)(+v) 

Отзывы: