LIGHT LEVEL FEATURE

INSTALLATION INSTRUCTIONS

         PS-P24-CM

360°

Passive Infrared Low Voltage Occupancy Sensor

With Light Level Feature

SPECIFICATIONS

-02- 

-03-

-01-

Voltage ......................................................................................................................... 24VDC

Current Consumption ....................................................................................................... 9mA

Power Supply .................................................................PS-PP3000/PS-PP7000 Power Packs

Adjustable Light Level ..........................................................................................10FC-150FC

Adjustable Time Delay .................................................................... 5 sec.-30min (DIP switch)

Walk-Through Mode .........................................................3 minutes if no activity after 30 sec.

Test Mode  ........................................................ 5 sec. upon initial power-up or DIP switch reset

PIR Coverage:

Sensitivity Adjustment  ............................................................. Automatic or Low (DIP switch)

Coverage............................................................................................................ Up to 1200 ft

2

The PS-P24-CM 360

°

passive infrared (PIR) occupancy sensors turn lighting systems on

and off based on occupancy and ambient light levels. The light level feature keeps lights from

turning on if the ambient light level is sufficient.

The sensors can be configured to turn lighting on, and hold it on as long as the sensor detects

occupancy. After no movement is detected for a user specified or Autoset time (5s to 30

minutes) the lights are switched off. A “walk-through” mode can turn lights off after only 3

minutes, if no activity is detected after 30 seconds of an occupancy detection.

The PS-P24-CM operates on 24V supplied by PS-PP3000/PS-PP7000 Power Packs.

DESCRIPTION

The PS-P24-CM provides a 360

°

coverage pattern, up to 1200 square feet. The coverage

shown represents walking motion at a mounting height of 8 feet. For building spaces with lower

levels of activity or with obstacles and barriers, coverage size may decrease.

COVERAGE PATTERN

Depending upon obstacles such as furniture or partitions, the area of coverage may be less or

more than the sensing distances shown in the coverage pattern. This must be considered

when planning the number of sensors and their placement. It is also recommended to place the

sensor 4 to 6 feet away from air supply ducts as rapid air currents or the differences in tem-

peratures may cause false activations.

PLACEMENT GUIDELINES

Mount the sensor to the ceiling. The PS-P24-CM is designed for a ceiling height of about

8-10 feet. Mounting above or below this range will significantly affect the coverage patterns. Be

aware that as you decrease the mounting height, you decrease the range and increase the

sensitivity to smaller motions. Conversely, when you increase the height, you increase the range

and decrease the sensitivity to smaller motions. At heights of more than 12-14 feet, you may start

44 ft
13.4m

8 ft

22 ft 

13 ft 

7 ft  3 ft  0  3 ft  7 ft 

13 ft 

22 ft

Typical

desk-top

level

Drawings not to scale.

12'

18'

3

WIRING DIRECTIONS

Each PS-PP3000 or PS-PP7000 power pack can supply power for 6 PS-P24-CM sensors. When
using more sensors than this, multiple power packs are required.

MOUNTING THE SENSOR

CAUTION!

TURN POWER OFF AT THE CIRCUIT BREAKER BEFORE INSTALLING

POWER PACKS OR SENSORS.

to significantly reduce sensitivity. As a general rule, each occupant should

be able to clearly view the sensor.

Often the best location to install a PS-P24-CM in a closed

office is off-center. Avoid placing a sensor directly in line with

an open door through which it has a clear view out, as the sen-

sor may detect people walking by.

C

o

m

m

o

n

+

2

4

V

D

C

M

a

n

u

a

l O

N

C

o

n

tr

o

l O

u

t

Operating Temperature .......................................................................32

 °

to 131

°

F (0

 °

to 55

 °

C)

adjacent sensor's coverage area.

multiple sensors so that there is an overlap with each

For large areas of coverage use multiple sensors.

Open Office Area Coverage:

To get complete coverage in an open office area, install

Connect the low voltage:

RED wire (+24VDC) from power pack to the +24V terminal on the sensor.

BLACK wire (Common) from power pack to Common terminal on the sensor.

Wiring a SINGLE LIGHTING LOAD CONTROLLED BY OCCUPANCY  - Connect:

BLUE wire from power pack to Control Out terminal on sensor.

Wiring multiple SINGLE LIGHTING LOADs CONTROLLED BY OCCUPANCY,  DEPENDENT

ON LIGHT LEVEL (AMBIENT LIGHT) - Connect:

BLUE wire from power pack to Control Out terminal on sensors.

To add a MANUAL SWITCH such as a Momentary Toggle Switch, to the above applications-

1. Wire from one side of switch to Common terminal on sensor.

2. Wire from other side of switch to Man Switch terminal on sensor.

Turn the potentiometer on the sensor to the "-"  if adequate ambient light exists, the output of

sensor will be inhibited, and the  load can not be on; only when the ambient light is down to a

certain level the sensor will automatically turn on. Therefore, potentiometers require custom-

ers to adjust in accordance with the location and the ambient light level. This feature can

effectively turn on the load when adequate ambient light exists, in order to achieve energy-

saving. Turn the potentiometer on the sensor to the "+", regardless of the ambient light level.

The load will be on as long as there are signals from occupancy.

+

Light

Avoid mounting the sensor close to lighting fixtures.

Adjust during daylight hours when ambient light in the area is at desired

level. Open the Front Cover and locate the Light Level. See Sensor

Adjustment.

Using an Octagonal J-Box

7. Snap the front cover onto the sensor.

J-Box  Mount

Front Cover

Rear Housing

Wire

Screws

4"Octagonal box 2-1/2" Deep
mounting

Drop Ceiling

1. Pull the low voltage wires from the power pack into the J-Box through the conduit knockout.

2. Connect the low voltage wires to the appropriate terminals on the sensor.
3. Loosen the appliance mounting screws attached to the J-Box.
4. Align the sensor in the J-Box so that the mounting screws on the box match the key holes on

the sensor’s rear housing.

5. Push the sensor up into the J-Box and  twist it so that the mounting screws are  seated in

the keyhole slots.

6. Tighten the two screws to secure the sensor to the J-Box.

PIR lens

PIR Activity LED(Red)

Light level Adjustment

Double gang mudring

mounting holes

DIP switches

Keyhole slots

Keyhole slots(for mounting to

4" octagonal box)

Load LED(Green)

Buzzer

(for mounting to 4" octagonal box)

connect:

PS-P24-CM

Ceiling  Mount  PIR  Occupancy  Sensor
PIR/Ceiling  Mount/Low  Voltage/360

Indoor Use Only

NexLight • 7877 College Road Suite 105 • Baxter MN 56425 • www.nexlight.com

Made  in  China

  PerfectSense

TM

Voltage:  24VDC
Current  Consumption:  9  mA
Power  Pack  Motor  Load:  1  HP;

PS-P24-CM

Ceiling  Mount  PIR  Occupancy  Sensor
PIR/Ceiling  Mount/Low  Voltage/360

Indoor Use Only

NexLight • 7877 College Road Suite 105 • Baxter MN 56425 • www.nexlight.com

Made in China

PerfectSense

TM

Voltage: 24VDC
Current  Consumption: 9  mA
Power Pack Motor Load: 1 HP;