Power Supply parameters
Parameter
Description
Default
Power mode
Sets the power mode.
• "Off": Power to any connected device is switched off.
There is no communication between adapter and any
connected device. Set this mode if the adapter is to be
used as a router.
• "Automatic": The connected device is powered-up
when an external master starts communicating with the
adapter. The device is powered after the last command
for a period determined by "Power On Time After
External Trigger".
• "Configuration": The connected device is powered-up
when the button on the adapter is pressed or an
external master communicates with it. The device is
powered after the last command for a period
determined by "Configuration Time". When this period
has elapsed, the power mode reverts to "Automatic"
Configu
ration
Field Device
Table
Displays the parameters read from the HART device by
the scan:
• Manufacturer ID: Manufacturer of connected device
• Expanded Device Type Code: Device identifier as per
HART
• Device ID: Manufacturer
’
s device identifier
• Universal Command Revision Level: HART revision
supported
• Long Tag: Long tag of device (Message for HART
revision < 6.0)
• * Start-Up Voltage: Voltage required to start the
connected device
• * Start-Up Time: Time required for the device to wake-
up
• * Start-Up Current: Current consumed on starting the
device
• * Lead Time: Time that elapses between start-up and
the point when the HART communication is
synchonized
* Parameters taken from DTM
–
Start-Up Voltage
Press this button to scan the connected device for its
parameters.
A scan is made every time the adapter is powered up after
connection of the battery. The table then fills automatically.
–
Start-Up Voltage
Voltage required by the connected device on start up.
Valid range 8 ... 23 V in steps of 0.1 V.
Filled automatically if the Field Device table is active.
16
Start-Up Time
Time in seconds required for the device to start up.
Filled automatically if the Field Device table is active.
5
Start-Up Current
Current in mA drawn by the connected device during start-
up.
Filled automatically if the Field Device table is active.
14
Operating
Voltage
Voltage connected device requires in normal operation.
Filled automatically if the Field Device table is active.
16