AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Configuration of AS-i/PROFINET Gateways
13.4.2
Manufacturer specific diagnostic
Slot
channel
code
message
PS
1
1.
PS: Slot of the PROFIsafe module
0
64
incorrect target address
65
invalid target address
66
invalid source address
67
invalid watchdog time
68
submitted SIL-class is too high
69
invalid CRC2-lenght
70
invalid PROFIsafe-version
71
CRC1 error
72
parameter setting inconsistent
75
iParCRC
Tab. 13-28.
Information!
Available only with AS-i/PROFIsafe Gateways.
AS-i flags
structure 0xA0: circuit 1
structure 0xA1: circuit 2
Byte
bit
message
0
0
config error
0
1
slave 0 detected
0
2
automatic addressing
not
possible
0
3
automatic addressing possible
0
4
configuration mode
0
5
no normal operation
0
6
AS-i power fail
0
7
off-line
1
0
peripheral fault
1
1
—
1
2
—
1
3
—
Tab. 13-29.