AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Electrical connection
9.10
Indicators and operating elements
9.10.1
LED indicators – master
The LED’s on the front panel of the device indicate:
PROFINET
Power
The master is receiving sufficient power.
PROFINET
Green: PROFINET controller connected (otherwise LED flashes red)
config error
Configuration error.
At least one configured slave is missing, or at least one detected slave is not config-
ured, or for at least one configured and detected slave the actual configuration data
does not match the nominal configuration data, or the master is in the startup pro-
cess.
This LED flashes if a peripheral fault has been detected for at least one AS-i slave
on the AS-i network. If there are configuration errors as well as periphery faults, only
the configuration error is displayed.
U AS-i
The AS-i network is sufficiently powered.
AS-i active
Normal operation is active
prg enable
Automatic single node replacement is enabled.
Exactly one slave is missing in the protected operating mode. The slave can be
replaced by another slave of the same type with address zero. The master automat-
ically addresses the new slave to the faulty address and thus corrects the configura-
tion error
prj mode
The AS-i master is in configuration mode.
Содержание VBG-PN-K30-D-S16
Страница 1: ...AS I 3 0 PROFINET GATEWAY WITH INTEGR SAFETY MONITOR FACTORY AUTOMATION MANUAL...
Страница 41: ...AS i 3 0 PROFINET Gateway with integr Safety Monitor Installation 27 9 2013 41 1 new old 2 3...
Страница 125: ...AS i 3 0 PROFINET Gateway with integr Safety Monitor Appendix Examples 27 9 2013 125...
Страница 126: ...27 9 2013 126 AS i 3 0 PROFINET Gateway with integr Safety Monitor Appendix Examples...
Страница 130: ......