AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Specifications - AS-i/PROFINET Gateways
27
.9.20
13
21
5.3.5
System reaction times – example calculations
System components:
ASI1
AS-i network 1
ASI2
AS-i network 2
S1-1
Safe sensor slave
(EMERGENCY-OFF switch: t
R S1-1
= 100 ms)
S1-2
Safe sensor slave
(safety light barrier: t
R S1-2
= 18 ms)
S2-1
Safe sensor slave
(EMERGENCY-OFF switch: t
R S2-1
= 100ms)
A2-1
Safe actuator slave
(motor starter: t
R A2-1
= 50ms)
SM1-1
Safety monitor with 16 relais circuits
and one safe AS-i output in AS-i
network 1
SM1-2
Safety monitor with 2 relais circuits
and one safe AS-i output in AS-i
network 1
SM2-1
Safety monitor with 16 relais circuits
and one safe AS-i output in AS-i
network 2
Tab. 5-6.
System configuration - example 1: Calculation of the system reaction time