AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Specifications - AS-i/PROFINET Gateways
27
.9.20
13
17
5.2
Safety-relevant characteristic data
Characteristic data
Value Standard
Safety category
4
EN 954-1
Safety category
4
EN ISO 13849-1: 2008
Performance Level (PL)
e
Safety Integrity Level (SIL)
3
EN 61508: 2001
Lifespan (TM) in years
20
EN ISO 13849-1: 2008
Maximum switch-on time in months
12
EN 61508: 2001
Max. system reaction time in
milliseconds
40
EN 61508: 2001
Tab. 5-3.
Attention!
In addition to the system reaction time of max. 40 ms, the reaction times of the safe AS-
interface sensor slave, of the sensor being used for monitoring, of the safe AS-interface
actuator slave and of the actuator used for this purpose must still be added. Please note
that additional reaction times may likewise arise through the configuration of the safety
monitor.
Notice!
Refer to the technical data for the slaves as well as to that for the sensors and actuators
for the reaction times to be added.
Attention!
The system reaction times of the daisy-chained AS-interface components are added up.