27
.9.20
13
128
AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Codes indicated by the display
20.
Codes indicated by the display
In the basic state of the configuration mode, the addresses of all detected slaves
are displayed in two-second intervals. A blank display indicates that the LDS (List
of Detected Slaves) is empty, no slaves were detected.
In the basic state of the protected operating mode, the display is either blank or
displays the address of a faulty assignment.
During manual address programming, the slave address display has a different
meaning (see also chapter "Operating in advanced display mode").
All displayed numbers bigger than 31 which can not be interpreted as a slave ad-
dress are status or error messages of the master. They have the following mean-
ings:
39
Advanced AS-i diagnostics: After pressing the ’set’-button a short-time AS-i
power failure occurred.
40
The AS-i master is in offline phase.
41
The AS-i master is in detection phase.
42
The AS-i master is in activation phase.
43
The AS-i master starts the normal operating mode.
68
Hardware error: disturbed internal communication.
69
Hardware error: disturbed internal communication.
70
Hardware error: The AS-i master’s EEPROM cannot be written.
71
Wrong PIC-type.
72
Hardware error: wrong PIC-processor.
73
Hardware error: wrong PIC-processor.
74
Checksum error in the EEPROM.
75
Error in the internal RAM.
76
Error in the external RAM.
77
AS-i control software error: Stack overflow (AS-i control II)
78
AS-i control software error: checksum error in the control program.
"control checksum":
checksumm in Control III C program (bin.file) not correct. The file is possibly
damaged.
"control exec err":
error in Control III C program.
"control watchdog":
watchdog predetermined in Control III C program has expired .
"control incomp":
Control III C program from another gateway type loaded (e.g. Ethernet IP in
Profibus gateway).
Содержание VBG-PN-K30-D-S16
Страница 1: ...AS I 3 0 PROFINET GATEWAY WITH INTEGR SAFETY MONITOR FACTORY AUTOMATION MANUAL...
Страница 41: ...AS i 3 0 PROFINET Gateway with integr Safety Monitor Installation 27 9 2013 41 1 new old 2 3...
Страница 125: ...AS i 3 0 PROFINET Gateway with integr Safety Monitor Appendix Examples 27 9 2013 125...
Страница 126: ...27 9 2013 126 AS i 3 0 PROFINET Gateway with integr Safety Monitor Appendix Examples...
Страница 130: ......