AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Configuration of AS-i/PROFINET Gateways
27
.9.20
13
103
Language
Selection of the displayed language.
Default: no change of the displayed language.
List of Configuration Errors
The AS-i/PROFINET Gateway saves a list of all AS-i slaves which have triggered
a present configuration error. This list can be sent with the PROFINET diagnostic
data.
Default: Transmission in the PROFINET diagnostic data.
List of Peripheral Faults
The AS-i/PROFINET Gateway saves a list of all AS-i slaves which have triggered
a peripheral errors. This list can be sent with the PROFINET diagnostic data.
Default: Transmission in the PROFINET diagnostic data.
Safety Status
Safety slaves whose device is in the red or yellow flashing state can be shown in
the diagnostics.
Default: Display of device status enabled in diagnostics.
Substitution values
Setting the substitution of input data for safety-relevant AS-i slaves:
13.6
Media Redundancy Protocol MRP
The AS-i/PROFINET Gateway supports Media Redundancy Protocol (MRP), a
protocol for highly available networks that can be used to compensate for single
failures in a ring topology.
To be a station in an MRP ring,
•
the Gateway must be configured using “DAP V2.25”, and
•
‘Client’ must be selected as the media redundancy role in the Properties for
the PROFINET interface.
Keep old value:
No change
No substitution values:
No substitution (code sequence)
Substitution values:
Substitution based on switching state
Diagnostic values:
Substitution based on switching state and associated
safety-relevant component
Information!
Please see section <Status indication, faults and fault elimination> for further codes
indicated by the display.
Содержание VBG-PN-K30-D-S16
Страница 1: ...AS I 3 0 PROFINET GATEWAY WITH INTEGR SAFETY MONITOR FACTORY AUTOMATION MANUAL...
Страница 41: ...AS i 3 0 PROFINET Gateway with integr Safety Monitor Installation 27 9 2013 41 1 new old 2 3...
Страница 125: ...AS i 3 0 PROFINET Gateway with integr Safety Monitor Appendix Examples 27 9 2013 125...
Страница 126: ...27 9 2013 126 AS i 3 0 PROFINET Gateway with integr Safety Monitor Appendix Examples...
Страница 130: ......