AS-Interface
Command Interface
Subject to reasonable modifications due to technical advances.
Copyright Fuchs, Printed in Germany
Fuchs Group · Tel.: Germany (6 21) 7 76-0 · USA (3 30) 4 25 35 55 · Singapore 7 79 90 91 · Internet http://www.pepperl-fuchs.com
Is
s
ue dat
e -
12.
8.
2007
112
• Select within the range
Data selection
sorted
(sorted by OSSD) or
unsorted
(all
devices)
Fig. 3. Data selection (sorted/unsorted)
10.4.2.2
Enhanced diagnosis
Since the "Safety at Work“ monitor diagnosis is longer than the maximum size of
the command interface, it must be read with several adjacent requests.
The byte 5 (‘index’) declares the start index in the array of diagnostic data. If this
start index is 0, the whole diagnosis is fetched from the monitor and stored to an
internal buffer. Otherwise, the AS-i Master will respond out of the internal buffer.
Thus, even though several requests are necessary to read the whole buffer, data
integrity is maintained.
Request
byte
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
1
7E
16
2
T
L
1
1. L=1 long diagnosis for advanced monitor
U
2
2. U=1 unsorted diagnosis (all devices)
circuit
3
02
16
4
slave address
5
index