Input
Programming instructions
Compliance with standards and directives
Ambient conditions
Number/Type
Four analog inputs
Current: 0 mA ... 20 mA/4 mA ... 20 mA
Supply
from AS-Interface (switch position INT, basic setting) or auxiliary
voltage U
EXT
(switch position EXT)
Current loading capacity
140 mA from AS-Interface; overload and short-circuit resistant
600 mA from external auxiliary voltage U
AUX
, overload and
short-circuit protected
Input resistance
Max. 70
Accuracy
0.1% of end value
Resolution
16 bits
Temperature influence
0.0025%/K from input signal range
Profile
S-7.3.E
IO code
7
ID code
3
ID2 code
E
Data bits (function via AS-
Interface)
The transfer of the data value is based on AS-Interface Profile
7.3.
Parameter bits
(programmable via AS-i)
function
P0
50/60 Hz filter
P0=1, enabled
P0=0, disabled
P1
Not used
P2
Indication of the peripheral fault by exceeding measuring range
P2=1, peripheral fault is reported
P2=0, peripheral fault is not reported
P3
P3=1, wire break detection active, automatic channel detection
(at > 1 mA)
P3=0, wire break detection deactivated, all four channels active
Directive conformity
EMC Directive
2004/108/EC
EN 50295:1999
Standard conformity
Noise immunity
EN 61000-6-2:2005, EN 61326-1:2006, IEC 62026-2:2008
Emitted interference
EN 61000-6-4:2007
Input
EN 61131-2:2007
Protection degree
EN 60529:2000
Fieldbus standard
EN 50295:1999, IEC 62026-2:2008
Ambient temperature
-25 ... 70
°
C (-13 ... 158
°
F)
Storage temperature
-25 ... 85
°
C (-13 ... 185
°
F)