
Safety Manual SIL KFD0-RSH-1(-Y2), KFD2-SL-4
Planning
2
014-07
7
2.2
Assumptions
The following assumptions have been made during the FMEDA analysis:
The device shall claim less than 10 % of the total failure budget for a SIL2
safety loop.
For a SIL2 application operating in Low Demand Mode the total PFD
avg
value
of the SIF (
S
afety
I
nstrumented
F
unction) should be smaller than 10
-2
, hence
the maximum allowable PFD
avg
value would then be 10
-3
.
For a SIL2 application operating in High Demand Mode of operation the total
PFH value of the SIF should be smaller than 10
-6
per hour, hence the
maximum allowable PFH value would then be 10
-7
per hour.
The device shall claim less than 10 % of the total failure budget for a SIL3
safety loop.
For a SIL3 application operating in Low Demand Mode the total PFD
avg
value
of the SIF (
S
afety
I
nstrumented
F
unction) should be smaller than 10
-3
, hence
the maximum allowable PFD
avg
value would then be 10
-4
.
For a SIL3 application operating in High Demand Mode of operation the total
PFH value of the SIF should be smaller than 10
-7
per hour, hence the
maximum allowable PFH value would then be 10
-8
per hour.
Failure rate based on the Siemens SN29500 data base.
Failure rates are constant, wear out mechanisms are not included.
External power supply failure rates are not included.
The safety-related device is considered to be of type
A
components with a
Hardware Fault Tolerance of
0
.
Since the loop has a Hardware Fault Tolerance of
0
and it is a type
A
component, the SFF must be > 60 % according to table 2 of IEC 61508-2 for a
SIL2 (sub)system.
Since the loop has a Hardware Fault Tolerance of
0
and it is a type
A
component, the SFF must be > 90 % according to table 2 of IEC 61508-2 for a
SIL3 (sub)system.
It is assumed that the device will be used under average industrial ambient
conditions, which are comparable with the classification "stationary mounted"
in MIL-HDBK-217F. Alternatively, the following ambient conditions are
assumed:
• IEC 60654-1 Class C (sheltered location) with temperature limits in the
range of the manufacturer's specifications and an average temperature
of 40
º
C over a long period. A moisture level within the manufacturer's
specifications is assumed. For a higher average temperature of 60
º
C,
the failure rates must be multiplied by a factor of 2.5 based on empirical
values. A similar multiplier must be used if frequent temperature
fluctuations are expected.
Содержание SIL KFD0-RSH-1
Страница 1: ...ISO9001 2 3 Relay Module KFD0 RSH 1 Y2 KFD2 SL 4 PROCESS AUTOMATION SAFETY MANUAL SIL...
Страница 18: ...2014 07 18 Safety Manual SIL KFD0 RSH 1 Y2 KFD2 SL 4 Notes Safety Manual SIL KFD0 RSH 1 Y2 KFD2 SL 4...
Страница 19: ...Safety Manual SIL KFD0 RSH 1 Y2 KFD2 SL 4 Notes 2014 07 19...