Useful Lifetime

Although a constant failure rate is assumed by the probabilistic estimation this only applies 

provided that the useful lifetime of components is not exceeded. Beyond this useful lifetime, 

the result of the probabilistic estimation is meaningless as the probability of failure significantly 

increases with time. The useful lifetime is highly dependent on the component itself 

and its operating conditions 

 temperature in particular. For example, electrolytic capacitors 

can be very sensitive to the operating temperature.
This assumption of a constant failure rate is based on the bathtub curve, 

which shows the typical behavior for electronic components.
Therefore it is obvious that failure calculation is only valid for components that have 

this constant domain and that the validity of the calculation is limited to the useful lifetime 

of each component.
It is assumed that early failures are detected to a huge percentage during the installation 

and therefore the assumption of a constant failure rate during the useful lifetime is valid.
However, according to IEC/EN 61508-2, a useful lifetime, based on general experience, 

should be assumed. Experience has shown that the useful lifetime often lies within a range 

period of about 8 to 12 years.
As noted in DIN EN 61508-2:2011 note N3, appropriate measures taken by the manufacturer 

and plant operator can extend the useful lifetime.
Our experience has shown that the useful lifetime of a Fuchs product can be higher 

if the ambient conditions support a long life time, for example if the ambient temperature 

is significantly below the maximum ambient temperature.
Please note that the useful lifetime refers to the (constant) failure rate of the device. 

The effective life time can be higher.
The estimated useful lifetime is greater than the warranty period prescribed by law 

or the manufacturer's guarantee period. However, this does not result in an extension 

of the warranty or guarantee services. Failure to reach the estimated useful lifetime 

is not a material defect.

Содержание SIL HiC2853R1

Страница 1: ...ISO9001 3 Functional Safety Switch Amplifier HiC2853R1 HiC2853R4 Manual...

Страница 2: ...ion as well as the supplementary clause Expanded reservation of proprietorship Worldwide Pepperl Fuchs Group Lilienthalstr 200 68307 Mannheim Germany Phone 49 621 776 0 E mail info de pepperl fuchs co...

Страница 3: ...on 8 2 2 Interfaces 8 2 3 Marking 8 2 4 Standards and Directives for Functional Safety 9 3 Planning 10 3 1 System Structure 10 3 2 Assumptions 11 3 3 Safety Function and Safe State 12 3 4 Characterist...

Страница 4: ...Functional Safety HiC2853R1 HiC2853R4 Contents 4 2022 06...

Страница 5: ...truction manual Manual Datasheet Additionally the following parts may belong to the documentation if applicable EU type examination certificate EU declaration of conformity Attestation of conformity C...

Страница 6: ...and understood the instruction manual and the further documentation Intended Use The device is only approved for appropriate and intended use Ignoring these instructions will void any warranty and ab...

Страница 7: ...are displayed in descending order as follows Informative Symbols Action This symbol indicates a paragraph with instructions You are prompted to perform an action or a sequence of actions Danger This s...

Страница 8: ...R1 The input controls one 24 V DC active voltage output and one passive transistor output with a resistive output characteristic The outputs have three defined states 1 Signal 6 5 V voltage drop 0 Sig...

Страница 9: ...s System specific standards and directives Functional safety IEC EN 61508 part 1 7 edition 2010 Functional safety of electrical electronic programmable electronic safety related systems manufacturer F...

Страница 10: ...usually the demand rate for this safety loop is assumed to be higher than once per year The relevant safety parameters to be verified are the PFH value Probability of dangerous Failure per Hour Fault...

Страница 11: ...r must be used if frequent temperature fluctuations are expected The indication of a dangerous failure via fault bus is detected within 1 hour by the programmable logic controller PLC Since the output...

Страница 12: ...I is high impedant The safe state for the electronic output output II is de energized The safe state will also be achieved if the device is not powered The output II safe state initiated by an input l...

Страница 13: ...utput s 186 FIT 145 FIT dd 0 FIT 0 FIT du 1 91 FIT 2 99 FIT total safety function 188 FIT 148 FIT total 437 FIT 437 FIT SFF 98 9 97 9 MTBF 1 1 acc to SN29500 This value includes failures which are not...

Страница 14: ...a electronic output Signal transfer via resistive transistor output s 187 FIT 146 FIT dd 0 FIT 0 FIT du 1 91 FIT 2 99 FIT total safety function 189 FIT 149 FIT total 439 FIT 440 FIT SFF 99 98 MTBF 1 2...

Страница 15: ...early failures are detected to a huge percentage during the installation and therefore the assumption of a constant failure rate during the useful lifetime is valid However according to IEC EN 61508...

Страница 16: ...instructions in the instruction manual 2 Observe the information in the manual 3 Observe the requirements for the safety loop 4 Connect the device only to devices that are suitable for this safety ap...

Страница 17: ...he applied PFDavg in accordance with the characteristic safety values See chapter 3 4 It is under the responsibility of the plant operator to define the type of proof test and the interval time period...

Страница 18: ...state is indicated by red LED and the outputs must be in fault state The resistive transistor output is high impedant 100 k and the voltage output is off 5 Test the output with a certain voltage HiC2...

Страница 19: ...U 1 3 k 0 5 W 2 k 0 5 W II I I supply Fault 24 V DC Power Supply HiC2853R4 Zone 0 1 2 Div 1 2 Zone 2 Div 2 Termination Board V SL1 8a 7a 10a 9a 11 14 12 15 1a 1b 2a 2b 6b 5a 5b 1 4 SL2 Multimeter I RL...

Страница 20: ...a defect always replace the device with an original device Reporting Device Failure If you use the device in a safety loop according to IEC EN 61508 it is required to inform the device manufacturer ab...

Страница 21: ...he safety loop total safety function Probability of failure of components that are in the safety loop HFT Hardware Fault Tolerance MTBF Mean Time Between Failures MTTR Mean Time To Restoration PCS Pro...

Страница 22: ...Pepperl Fuchs Quality Download our latest policy here www pepperl fuchs com quality www pepperl fuchs com Pepperl Fuchs Subject to modifications Printed in Germany DOCT 3712A...

Отзывы: