Functional Safety HiC2853R1, HiC2853R4

Planning

3

Planning

3.1

System Structure

3.1.1

Low Demand Mode of Operation

If there are two control loops, one for the standard operation and another one 

for the functional safety, then usually the demand rate for the safety loop is assumed to be less 

than once per year.
The relevant safety parameters to be verified are:

the PFD

avg

 value (average 

P

robability of dangerous 

F

ailure on 

D

emand) 

and the T

1

 value (proof test interval that has a direct impact on the PFD

avg

value)

the SFF value (

S

afe 

F

ailure 

F

raction)

the HFT architecture (

H

ardware 

F

ault 

T

olerance)

3.1.2

High Demand or Continuous Mode of Operation

If there is only one safety loop, which combines the standard operation and safety-related 

operation, then usually the demand rate for this safety loop is assumed to be higher 

than once per year.
The relevant safety parameters to be verified are:

the PFH value (

P

robability of dangerous 

F

ailure per 

H

our)

Fault reaction time of the safety system 

the SFF value (

S

afe 

F

ailure 

F

raction)

the HFT architecture (

H

ardware 

F

ault 

T

olerance)

3.1.3

Safe Failure Fraction

The safe failure fraction describes the ratio of all safe failures and dangerous detected failures 

to the total failure rate.
SFF = (

s

 + 

dd

) / (

s

 + 

dd

 + 

du

)

A safe failure fraction as defined in IEC/EN 61508 is only relevant for elements or (sub)systems 

in a complete safety loop. The device under consideration is always part of a safety loop 

but is not regarded as a complete element or subsystem.
For calculating the SIL of a safety loop it is necessary to evaluate the safe failure fraction 

of the elements and subsystems, but not of a single device.
Nevertheless the SFF of the device is given in this document for reference.

Содержание SIL HiC2853R1

Страница 1: ...ISO9001 3 Functional Safety Switch Amplifier HiC2853R1 HiC2853R4 Manual...

Страница 2: ...ion as well as the supplementary clause Expanded reservation of proprietorship Worldwide Pepperl Fuchs Group Lilienthalstr 200 68307 Mannheim Germany Phone 49 621 776 0 E mail info de pepperl fuchs co...

Страница 3: ...on 8 2 2 Interfaces 8 2 3 Marking 8 2 4 Standards and Directives for Functional Safety 9 3 Planning 10 3 1 System Structure 10 3 2 Assumptions 11 3 3 Safety Function and Safe State 12 3 4 Characterist...

Страница 4: ...Functional Safety HiC2853R1 HiC2853R4 Contents 4 2022 06...

Страница 5: ...truction manual Manual Datasheet Additionally the following parts may belong to the documentation if applicable EU type examination certificate EU declaration of conformity Attestation of conformity C...

Страница 6: ...and understood the instruction manual and the further documentation Intended Use The device is only approved for appropriate and intended use Ignoring these instructions will void any warranty and ab...

Страница 7: ...are displayed in descending order as follows Informative Symbols Action This symbol indicates a paragraph with instructions You are prompted to perform an action or a sequence of actions Danger This s...

Страница 8: ...R1 The input controls one 24 V DC active voltage output and one passive transistor output with a resistive output characteristic The outputs have three defined states 1 Signal 6 5 V voltage drop 0 Sig...

Страница 9: ...s System specific standards and directives Functional safety IEC EN 61508 part 1 7 edition 2010 Functional safety of electrical electronic programmable electronic safety related systems manufacturer F...

Страница 10: ...usually the demand rate for this safety loop is assumed to be higher than once per year The relevant safety parameters to be verified are the PFH value Probability of dangerous Failure per Hour Fault...

Страница 11: ...r must be used if frequent temperature fluctuations are expected The indication of a dangerous failure via fault bus is detected within 1 hour by the programmable logic controller PLC Since the output...

Страница 12: ...I is high impedant The safe state for the electronic output output II is de energized The safe state will also be achieved if the device is not powered The output II safe state initiated by an input l...

Страница 13: ...utput s 186 FIT 145 FIT dd 0 FIT 0 FIT du 1 91 FIT 2 99 FIT total safety function 188 FIT 148 FIT total 437 FIT 437 FIT SFF 98 9 97 9 MTBF 1 1 acc to SN29500 This value includes failures which are not...

Страница 14: ...a electronic output Signal transfer via resistive transistor output s 187 FIT 146 FIT dd 0 FIT 0 FIT du 1 91 FIT 2 99 FIT total safety function 189 FIT 149 FIT total 439 FIT 440 FIT SFF 99 98 MTBF 1 2...

Страница 15: ...early failures are detected to a huge percentage during the installation and therefore the assumption of a constant failure rate during the useful lifetime is valid However according to IEC EN 61508...

Страница 16: ...instructions in the instruction manual 2 Observe the information in the manual 3 Observe the requirements for the safety loop 4 Connect the device only to devices that are suitable for this safety ap...

Страница 17: ...he applied PFDavg in accordance with the characteristic safety values See chapter 3 4 It is under the responsibility of the plant operator to define the type of proof test and the interval time period...

Страница 18: ...state is indicated by red LED and the outputs must be in fault state The resistive transistor output is high impedant 100 k and the voltage output is off 5 Test the output with a certain voltage HiC2...

Страница 19: ...U 1 3 k 0 5 W 2 k 0 5 W II I I supply Fault 24 V DC Power Supply HiC2853R4 Zone 0 1 2 Div 1 2 Zone 2 Div 2 Termination Board V SL1 8a 7a 10a 9a 11 14 12 15 1a 1b 2a 2b 6b 5a 5b 1 4 SL2 Multimeter I RL...

Страница 20: ...a defect always replace the device with an original device Reporting Device Failure If you use the device in a safety loop according to IEC EN 61508 it is required to inform the device manufacturer ab...

Страница 21: ...he safety loop total safety function Probability of failure of components that are in the safety loop HFT Hardware Fault Tolerance MTBF Mean Time Between Failures MTTR Mean Time To Restoration PCS Pro...

Страница 22: ...Pepperl Fuchs Quality Download our latest policy here www pepperl fuchs com quality www pepperl fuchs com Pepperl Fuchs Subject to modifications Printed in Germany DOCT 3712A...

Отзывы: