Operation and Communication
5.1.4
PROFINET Address and Identifying a Device
Every PROFINET IO has a unique device identification. This device identification consists of
the following:
■
A unique
MAC address
. This MAC address is printed on the back of the device.
■
A
device name
. The default device name is
pcv-f200
.
■
An
IP address
. The default IP address is
192.168.2.2
.
5.1.5
PROFINET Modules
1 word = 16-bit value
1 byte = 8-bit value
Modules with response telegram
The following modules enable reader data to be retrieved using PROFINET.
Position Data X Module
Response
Size
Type
Content
2 words,
consistent
Input data
32-bit X data
MSB first
MSB =
m
ost
s
ignificant
b
yte
Resolution: 0.1 mm, 1 mm, 10 mm, binary coded
At a resolution of 1 mm and 10 mm: L
max =
10.00 km =
10,000,000 mm
Bit No.
Content
Word 1
X Data
Word 2
X Data
1
XP16
XP00
2
XP17
XP01
3
XP18
XP02
4
XP19
XP03
5
XP20
XP04
6
XP21
XP05
7
XP22
XP06
8
XP23
XP07
9
XP24
XP08
10
XP25
XP09
11
XP26
XP10
12
XP27
XP11
13
XP28
XP12
14
XP29
XP13
15
XP30
XP14
16
XP31
XP15