Pulscon LTC57 PROFIBUS PA
Operating menu
Confirm probe length
Blocking
Navigation
Setup
Advanced setup
Probe settings
Confirm length
Description
Select, whether the value displayed in the
Present probe length
parameter
(page 129) matches the actual length of the probe. Based on this input, the device
performs a probe length correction.
Selection
• Probe length OK
• Probe length too small
• Probe length too big
• Probe covered
• Manual input
• Probe length unknown
Factory setting
Probe length OK
Additional information
Meaning of the options
•
Probe length OK
To be selected if the indicated length is correct. An adjustment is not required.
The device quits the sequence.
•
Probe length too small
To be selected if the displayed length is smaller than the actual length of the
probe. A different end of probe signal is allocated and the newly calculated
length is displayed in the
Present probe length
parameter (page 129). This
procedure has to be repeated until the displayed value matches the actual
length of the probe.
•
Probe length too big
To be selected if the displayed length is bigger than the actual length of the
probe. A different end of probe signal is allocated and the newly calculated
length is indicated in the
Present probe length
parameter (page 129). This
procedure has to be repeated until the displayed value matches the actual
length of the probe.
•
Probe covered
To be selected if the probe is (partially or completely) covered. A probe length
correction is impossible in this case. The device quits the sequence.
•
Manual input
To be selected if no automatic probe length correction is to be performed.
Instead, the actual length of the probe must be entered manually into the
Present probe length
parameter (page 129)
a
.
•
Probe length unknown
To be selected if the actual length of the probe is unknown. A probe length
correction is impossible in this case. The device quits the sequence.
a
When operated via PACTware, the
Manual input
option needs not to be selected explicitly. In PACTware the length of the probe can
always be edited.
Содержание Pulscon LTC57
Страница 173: ...Pulscon LTC57 PROFIBUS PA Notes 2015 03 173...
Страница 174: ...2015 03 174 Pulscon LTC57 PROFIBUS PA Notes...
Страница 175: ...Pulscon LTC57 PROFIBUS PA Notes 2015 03 175...