Pulscon LTC57 PROFIBUS PA
Operating menu
2015
-0
3
115
Blocking distance
Figure 15.5
Blocking distance (UB) for bulk solid measurements
Level correction
Blocking
Navigation
Setup
Advanced setup
Level
Blocking dist.
Description
Specify upper blocking distance UB.
User entry
0 to 200 m
Factory setting
• For coax probes: 0 mm (0 in)
• For rod and rope probes up to 8 m (26 ft): 200 mm (8 in)
• For rod and rope probes above 8 m (26 ft): 0.025 x length of probe
Additional information
No echoes are evaluated within the blocking distance UB. Therefore, UB can be
used to suppress interference echos within the upper end of the probe.
UB
Blocking
Navigation
Setup
Advanced setup
Level
Level correction
Description
Specify level correction (if required).
User entry
-200000.0 to 200000.0 %
Factory setting
0.0 %
Additional information
The value specified in this parameter is added to the measured level (before
linearization).