Power Supply PS1000-A6-24.20
Protection Features
20
21
-1
1
29
19
Protection Features
Output over-voltage protection Typ. 30.5Vdc
Max. 32Vdc
In case of an internal defect, a redundant circuit
limits the maximum output voltage. The output
shuts down and automatically attempts to restart.
Degree of protection
IP 20
EN/IEC 60529
Penetration protection
> 5mm
E.g. screws, small parts
Over-temperature protection
Included
Output shuts down with automatic restart.
Temperature sensors are installed on critical
components inside the unit and turn the unit off
in safety critical situations, which can happen
e.g. when ambient temperature is too high,
ventilation is obstructed or the derating
requirements are not followed.
There is no correlation between the operating
temperature and turn-off temperature since this
is dependent on input voltage, load
and installation methods.
Input transient protection
MOV
(Metal Oxide Varistor)
For protection values see chapter 17 (EMC).
Internal input fuse
Included
Not user replaceable slow-blow high-braking
capacity fuse