PS1000-A6-24.10
Power Supply

Technical Information

Содержание PS1000-A6-24.10

Страница 1: ...ISO9001 PS1000 A6 24 10 Power Supply Technical Information...

Страница 2: ...ion as well as the supplementary clause Expanded reservation of proprietorship Worldwide Pepperl Fuchs Group Lilienthalstr 200 68307 Mannheim Germany Phone 49 621 776 0 E mail info de pepperl fuchs co...

Страница 3: ...Time 15 10 DC OK Relay Contact 16 11 Efficiency and Power Losses 17 12 Lifetime Expectancy 19 13 MTBF 20 14 Terminals and Wiring 21 15 Functional Diagram 23 16 Front Side and User Elements 24 17 EMC 2...

Страница 4: ...Power Supply PS1000 A6 24 10 Contents 4 2021 11...

Страница 5: ...his information does not represent a warranty in the legal sense of the word As the state of our knowledge and experience is constantly changing the information in this data sheet is subject to revisi...

Страница 6: ...oltage with standard tolerances usually 15 included E g DC 12V describes a 12V battery disregarding whether it is full 13 7V or flat 10V 230Vac A figure with the unit Vac at the end is a momentary fig...

Страница 7: ...human life Function The device is used to supply field devices with 24 V DC and 10 A The device has a power reserve of 20 included which may even be used continuously at temperatures up to 45 C The ou...

Страница 8: ...vided for the output of the power supplies when used in applications according to CSA C22 2 No 107 1 01 Warning Risk of electrical shock fire personal injury or death Do not use the power supply witho...

Страница 9: ...0V Input current Typ 2 60A 2 15A 1 13A At 24V 10A see Figure 5 3 Power factor 1 Typ 0 99 0 99 0 97 At 24V 10A see Figure 5 4 Crest factor 2 Typ 1 5 1 5 1 65 At 24V 10A Start up delay Typ 300ms 290ms 2...

Страница 10: ...Power factor vs output current at 24V output voltage S tart up delay R is e Time Overshoot 5 Output Voltage Input Voltage 12A 1 2 3 4 5 6 7 8 9 0 0 5 1 0 1 5 2 0 2 5 3A Input C urrent typ 10 11 a 100V...

Страница 11: ...nd pole to N 3 Connect the PE terminal to an earth wire or to the machine ground DC input Nom DC 110 150V 20 DC input range Min 88 180Vdc Continuous operation DC input current Typ 2 35A At 110Vdc at 2...

Страница 12: ...e 7 1 Typical turn on behavior at nominal load 120Vac input and 25 C ambient Figure 7 2 Typical turn on behavior at nominal load 230Vac input and 25 C ambient AC 100V AC 120V AC 230V Inrush current Ma...

Страница 13: ...ee chapter 26 1 for more peak current measurements For AC 100V mains the pulse length is shorter than 12ms Overload behavior Continuous current Output voltage above 13Vdc see Figure 8 1 Hiccup mode 2...

Страница 14: ...ode typ Output Voltage 0 0 12 5 4 8 12 28V 16 20 24 20A 7 5 2 5 5 10 15 17 5 Adjus tment R ange Output C urrent C ontinuous current F actory s etting HiccupP LUS mode Output Voltage dynamicbehavior 12...

Страница 15: ...p Time Typ 73ms 73ms 73ms At 24V 5A see Figure 9 1 Min 55ms 55ms 55ms At 24V 5A see Figure 9 1 Typ 37ms 37ms 37ms At 24V 10A see Figure 9 1 Min 28ms 28ms 28ms At 24V 10A see Figure 9 1 0 10 20 30 40 8...

Страница 16: ...the adjusted output voltage level Contact opens As soon as the output voltage dips more than 10 below the adjusted output voltage Short dips will be extended to a signal length of 100ms Dips shorter t...

Страница 17: ...p 9 8W 8 9W 7 1W At 24V 5A Typ 18 3W 16 4W 12 1W At 24V 10A Typ 23 4W 21 7W 14 8W At 24V 12A Power Boost 1 The average efficiency is an assumption for a typical application where the power supply is l...

Страница 18: ...r Losses Figure 11 3 Efficiency vs input voltage at 24V 10A typ Figure 11 4 Losses vs input voltage at 24V 10A typ E fficiency 120 180 230 264Vac 90 91 92 93 Input Voltage 94 95 96 100 P ower L osses...

Страница 19: ...s manufacturer specification The manufacturer of the electrolytic capacitors only guarantees a maximum life of up to 15 years 131 400h Any number exceeding this value is a calculated theoretical lifet...

Страница 20: ...fail every 100 hours if 10 000 units are installed in the field However it cannot be determined if the failed unit has been running for 50 000h or only for 100h For these types of units the MTTF Mean...

Страница 21: ...next is allowed as long as the average output current through one terminal pin does not exceed 25A If the current is higher use a separate distribution terminal block as shown in Figure 14 2 Figure 14...

Страница 22: ...2021 11 22 Power Supply PS1000 A6 24 10 Terminals and Wiring Figure 14 2 Using distribution terminals Dis tribution Terminals L oad P ower S upply Output P ower S upply Output...

Страница 23: ...diagram Output Over Voltage P rotection P F C C onverter Output Voltage R egulator P ower C onverter Output F ilter Output Voltage Monitor Output P ower Manager T emper ature S hut down Input F us e...

Страница 24: ...meter Open the flap to adjust the output voltage Factory set 24 1V 3 DC OK LED green On when the output voltage is in range and the DC OK contact is closed 4 DC OK Relay Contact Push in terminals Moni...

Страница 25: ...tage sags SEMI F47 0706 Dips on the input voltage according to SEMI F47 standard 80 of 120Vac 96Vac 70 of 120Vac 84Vac 50 of 120Vac 60Vac 1000ms 500ms 200ms Criterion A Criterion A Criterion A Powerfu...

Страница 26: ...2021 11 26 Power Supply PS1000 A6 24 10 EMC Switching Frequencies PFC converter 110kHz Fixed frequency Main converter 84kHz to 140kHz Output load dependent Auxiliary converter 60kHz Fixed frequency...

Страница 27: ...titude de rating 15W 1 000m or 5 C 1 000m Above 2 000m 6 560ft see Figure 18 2 Over voltage category III According to IEC 62477 1 for altitudes up to 2000m II According to IEC 62477 1 for altitudes fr...

Страница 28: ...r Supply PS1000 A6 24 10 Environment Figure 18 2 Output current vs altitude 0 0 2000m 4000m 6000m 2A 4A 6A 8A 10A 12A Allowed Output C urrent at 24V Altitude B C A Tamb 60 C B Tamb 50 C C Tamb 40 C D...

Страница 29: ...E g screws small parts Over temperature protection Yes Output shut down with automatic restart The temperature sensor is installed on critical components inside the unit and turns the unit off in saf...

Страница 30: ...0Vdc 500MOhm At delivered condition between output and PE measured with 500Vdc 500MOhm At delivered condition between output and DC OK contacts measured with 500Vdc PE resistance 0 1Ohm Resistance bet...

Страница 31: ...testing input to DC OK ensure that the max voltage between DC OK and the output is not exceeded column D We recommend connecting DC OK pins and the output pins together when performing the test To fu...

Страница 32: ...gory NMTR UL 61010 2 201 Electrical Equipment for Measurement Control and Laboratory Use Particular requirements for control equipment Applicable for US and Canada E Files E350173 E223176 EN 60079 0 2...

Страница 33: ...tion of the use of certain hazardous substances in electrical and electronic equipment REACH Directive Directive 1907 2006 EU of the European Parliament and the Council of June 1st 2007 regarding the...

Страница 34: ...ht 124mm 4 88 inch Depth 117mm 4 61 inch The DIN mounting rail height must be added to the unit depth to calculate the total required installation depth Weight 600g 1 3lb DIN mounting rail Use 35mm DI...

Страница 35: ...does not require an additional auxiliary voltage and is self powered even in case of a short circuit across the output Due to the low power losses the unit is very slender and only requires 32mm widt...

Страница 36: ...bsequent circuit breakers of load circuits The load branches are often individually protected with circuit breakers or fuses In case of a short or an overload in one branch circuit the fuse or circuit...

Страница 37: ...o the built in large sized output capacitor which is specified in chapter 8 26 3 External Input Protection The unit is tested and approved for branch circuits up to 30A UL and 32A IEC An external prot...

Страница 38: ...his requires power supplies with high current reserves and large output capacitors Furthermore the impedance of the faulty branch must be sufficiently small in order for the current to actually flow T...

Страница 39: ...output is required when the sum of the output voltage is above 60Vdc Avoid return voltage e g from a decelerating motor or battery which is applied to the output terminals Restrictions Keep an instal...

Страница 40: ...ed on each output Alternatively a diode or redundancy module can also be utilized Energize all units at the same time to avoid the overload Hiccup mode It also might be necessary to cycle the input po...

Страница 41: ...refore use the DC OK signal of the device It is desirable to set the output voltages of all devices to the same value 100mV or leave it at the factory setting N 1 Redundancy Redundant systems for a hi...

Страница 42: ...table below 2 Use a 15A or 16A circuit breaker or blocking diode between the power supply and the battery 3 Ensure that the output current of the power supply is below the allowed charging current of...

Страница 43: ...istance of 1cm 26 12 Mounting Orientations Mounting orientations other than all terminals on the bottom require a reduction in continuous output power or a limitation in the maximum allowed ambient te...

Страница 44: ...n E horizontal ccw P ower S upply OUTP UT INP UT Output C urrent 0 10 20 30 40 60 C 3 6 9 12A 50 A1 Ambient T emperature Pow er Supply OUTPUT INPUT Output C urrent 0 10 20 30 40 60 C 3 6 9 12A 50 Ambi...

Страница 45: ...Power Supply PS1000 A6 24 10 Notes 2021 11 45...

Страница 46: ...Pepperl Fuchs Quality Download our latest policy here www pepperl fuchs com quality www pepperl fuchs com Pepperl Fuchs Subject to modifications Printed in Germany DOCT 7492...

Отзывы: