Power Supply PS1000-A6-12.16
Output
20
21
-1
1
13
8
Output
Output voltage
Nom. 12Vdc
Adjustment range
Min.
12-15Vdc
Guaranteed value
Max. 16.5Vdc
This is the maximum output voltage which can
occur at the clockwise end position of the
potentiometer due to tolerances. It is not a
guaranteed value which can be achieved.
Factory settings
Typ.
12.0Vdc ±0.2%
At full load and cold unit
Line regulation
Max. 10mV
Between 85 and 300Vac
Load regulation
Max. 50mV
Between 0 and 19.2A, static value, see Figure 8.1
Ripple and noise voltage Max. 50mVpp
Bandwidth 20Hz to 20MHz, 50Ohm
Output current
Nom. 19.2A
1
At 12V and an ambient temperature below 45°C,
see Figure 19.1
Nom. 16A
At 12V and 60°C ambient temperature,
see Figure 8.1
Nom. 12A
At 12V and 70°C ambient temperature,
see Figure 19.1
Nom. 15.4A
1
At 15V and an ambient temperature below 45°C,
see Figure 19.1
Nom. 12.8A
At 15V and 60°C ambient temperature,
see Figure 8.1
Nom. 9.6A
At 15V and 70°C ambient temperature,
see Figure 19.1
Typ.
48A
For minimal 12ms once every five seconds,
see Figure 8.2.
The output voltage stays above 10V.
See chapter 27.1 for more peak current
measurements. For AC 100V mains, the pulse
length is shorter than 12ms.
Overload behaviour
Continuous current
Output voltage above 6.5Vdc, see Figure 8.1
Hiccup
mode
2
Output voltage below 6.5Vdc, see Figure 8.1
Short-circuit current
Min.
20.5A
3
Load impedance <30mOhm, see Figure 8.3
Max. 25.5A
3
Load impedance <30mOhm, see Figure 8.3
Max. 7.3A
Average (R.M.S.) current, load impedance
50mOhm, see Figure 8.3
Min.
50A
Up to 12ms, load impedance <30mOhm,
see Figure 8.2
Typ.
55A
Up to 12ms, load impedance <30mOhm,
see Figure 8.2
Output capacitance
Typ.
5 350µF
Included inside the power supply
1
Power boost
This power/ current is continuously allowed up to an ambient temperature of 45°C.
Above 45°C, do not use this power/ current longer than a duty cycle of 10% and/ or not longer than 1 minute every 10 minutes.
2
Hiccup mode
At heavy overloads (when output voltage falls below 6.5V), the power supply delivers continuous output current for 2s.
After this, the output is switched off for approx. 18s before a new start attempt is automatically performed.
This cycle is repeated as long as the overload exists. If the overload has been cleared, the device will operate normally.
See Figure 8.3
3
Discharge current of output capacitors is not included.