Installation and Commissioning
2
016-
06
27
4.7
Gateway Configuration
You can configure the gateway only via the PROFINET IO engineering station. In order to view
the parameters in read-only status, use the web server or the gateway device type manager.
4.8
Gateway Device Parameters (DAP Submodules)
4.9
PROFIBUS PA Master Parameters (FAP Submodules)
Almost all PROFIBUS PA master parameters are set to default values and cannot be changed.
Only the values
“
maximum retry limit
”
and
“
watchdog time
”
can be changed. We recommend to
configure no less than 4 retries when operating the PROFIBUS PA installation, provided that
any of the following operation conditions apply:
■
High level of environmental impact
■
Vibration or shock
■
Field devices connecting or disconnecting regularly during operational conditions
The PA master address for each segment is fixed to "1".
4.10
Start-Up Behavior
After powering the Power Hub, the gateway starts to poll for connected PROFIBUS PA devices
in order to generate a live list. If a connection to a PROFINET IO controller and the
PROFIBUS PA devices are configured in the PROFINET IO system, the gateway starts the
IO cycle on the PROFIBUS PA segments.
Parameter
Description
Values
ADM alarm observer Disables/enables the mapping of the
advanced physical layer alarms to PROFINET
IO alarms. Prerequisites: An advanced
diagnostic module is used and appropriate
alarm limits are defined. See HD2-DM-A
documentation.
0: Disabled
1: Enabled
Default: Disabled
SNTP mode
Setting the
“
Simple Network Time Protocol
”
server. Match the configuration of the time
server used with this setting.
If an SNTP server is activated, the time is
synchronized with the advanced diagnostic
module to timestamp diagnostic events. Refer
to the manual of the SNTP server you are
using.
0: Disabled
1: Poll
2: Listen
Default: Listen
SNTP server IP 1
IP address for SNTP time server 1
Default value 0.0.0.0
SNTP server IP 2
IP address for SNTP time server 2
Default value 0.0.0.0
Parameter
Description
Values
Retry limit
Number of repeated telegrams before a
device is dropped from the life list
Min.: 1
Max.: 7
Default: 4
Watchdog time
PA segment watchdog
Min.: 100 ms
Max.: 20 000 ms
Default: 3000 ms