15
e
8
Functional display
LUC-T differentiates between the
operational faults alarm and warning.
(See also "Information on the
measuring point" page 28.)
2-Wire
If the LUC-T identifies an alarm
• the bargraph flashes, if the display is
plugged
• the current output adopts a
preselected value (-10 % = 3.8 mA,
+110 %, HOLD)
• an error code is output in V9H0
If the LUC-T identifies a warning
• the instrument continues to measure
• an error code is output in V9H0
4-Wire
If the LUC-T identifies an alarm
• the bargraph flashes, if the display is
plugged
• the red LED lights up
• the current output adopts a
preselected value (-10 % = 2.4 mA,
+110 %, HOLD)
• an error code is output in V9H0
If the LUC-T identifies a warning
• the red LED flashes
• the instrument continues to measure
an error code is output in V9H0
Function
green LED
red LED
Bargraph in
display
Error code in
V9H0?
Caution 2-wire versions: The green LED is not used to display operational status due to power
consumption. There is no red LED
2-Wire
Entry completed
Error status
• Alarm
• Warning
YES
YES
4-Wire
Entry completed
Error status
• Alarm
• Warning
YES
YES
V H
9
0
E 6 2 0
LED off
LED on
Содержание LUC-T Series
Страница 3: ...d KA 042O 98 de 07 01 Software 2 2 52010959 LUC T10 LUC T20 LUC T30 F llstandmessung mit Ultraschall d...
Страница 38: ...36...
Страница 39: ...e KA 042O 98 en 07 01 Software 2 2 52010959 LUC T10 LUC T20 LUC T30 Ultrasonic level measurement e...
Страница 74: ...36...
Страница 75: ...f KA 0420 98 fr 07 01 Software 2 2 52010959 LUC T10 LUC T20 LUC T30 Mesure de niveau ultrasonique f...
Страница 110: ...36...